Page 19 - Catalog Softstarters PSR PSE PSTX
P. 19

PSR – The compact range

         Ordering details



                                    Description
                                    Selection table for normal start. Typical applications:
                                       – Bow thruster
                                       – Centrifugal pump
                    1SFC132020V0001    – Compressor                                                                 2
                                       – Conveyor belt (short)
                                       – Elevator
            PSR3 ... PSR16          For a more precise selection, use the online softstarter selection tool available by scanning the shown QR
                                    code or using the selection tool available on:
                                    new.abb.com/low-voltage/products/softstarters
                    1SFC132072V0001  Rated operational voltage U , 208...600 V AC
                                                         e
                                                          s
 Normal start   PSR3  PSR6  PSR9  PSR12  PSR16 PSR25  PSR30  PSR37  PSR45  PSR60  PSR72  PSR85  PSR105  Rated control supply voltage, U , 100...240 V AC, 50/60 Hz  Type  Order code  Weight
                                    IEC
                                                       UL/CSA
 In-line connected  PSR25 ... PSR30
 (400 V) kW  1.5  3  4   5.5  7.5  11  15  18.5  22  30  37  45  55  Rated operational  Rated operational  pkg
 IEC, max. A  3.9  6.8  9  12  16  25  30  37  45  60  72  85  105  power  400 V 500 V  current power  current  (1 pce)
                                    230 V
                                                       200 /  220 /  440 /   550 /
 (440-480 V) hp  2  3  5  7.5  10  15  20  25  30  40  50  60  75  208 V 240 V 480 V 600 V
 UL, max. FLA  3.4  6.1  9  11  15.2  24.2  28  34  46.2  59.4  68  80  104  P e  P e  P e  I e  P e  P e  P e  P e  FLA
 400 V, 40 ºC       1SFC132024V0001  kW  kW  kW   A    hp  hp   hp  hp   A                               kg   (lb)
 Using manual motor   Manual motor starter (50 kA)   0.75  1.5  2.2  3.9  0.5  0.75  2  2  3.4  PSR3-600-70  1SFA896103R7000  0.45  (0.99)
 starters type 1 coordina-          1.5  3   4    6.8  1   1.5  3   5    6.1  PSR6-600-70  1SFA896104R7000  0.45  (0.99)
 tion will be achieved   1)  MS116  MS132  MS450  MS495  —  PSR37 ... PSR45  2.2  4  4  9  2  2  5  7.5  9  PSR9-600-70  1SFA896105R7000  0.45  (0.99)
                                    3    5.5  5.5  12  3   3    7.5  10  11   PSR12-600-70  1SFA896106R7000  0.45  (0.99)
 Using gG fuses type 1   Fuse protection (50 kA) gG Fuse  4  7.5  7.5  16  3  5  10  10  15.2  PSR16-600-70  1SFA896107R7000  0.45  (0.99)
 coordination will be               5.5  11  15   25   7.5  7.5  15  20  24.2  PSR25-600-70  1SFA896108R7000  0.65  (1.43)
 achieved  1)  10 A  16 A  25 A  32 A  50 A  63 A  100 A  125 A  200 A  250 A  7.5  15  18.5  30  7.5  10  20  25  28  PSR30-600-70  1SFA896109R7000  0.65  (1.43)
                                                                              PSR37-600-70
                                                                         34
                                                                    30
                                                                25
                                                       10
                                                           10
                                                  37
                                         18.5
                                             22
                                    7.5
                                                                                                         1.00
                                                                                                              (2.20)
                                                                                        1SFA896110R7000
 Suitable switch fuse for the  Switch fuse  1SFC132028V0001  11  22  30  45  15  15  30  40  46.2  PSR45-600-70  1SFA896111R7000  1.00  (2.20)
 above gG fuses  1)  OS32G  OS125G  OS250  15  30  37  60  20  20  40  50  59.4  PSR60-600-70  1SFA896112R7000  2.20  (4.85)
                                             45
                                                  72
                                                                                        1SFA896113R7000
                                                           25
                                                                                                              (5.00)
                                                                                                         2.27
                                                       20
                                         37
                                                                50
                                    22
                                                                    60
                                                                              PSR72-600-70
                                                                         68
                                    22   45  55   85   25  30   60  75   80   PSR85-600-70  1SFA896114R7000  2.27  (5.00)
 J-type fuses for UL    Max. fuse, J-type  PSR60 ... PSR105  30  55  55  105  30  40  75  100  104  PSR105-600-70 1SFA896115R7000  2.27  (5.00)
 coordination  1)  35 A  60 A  90 A  110 A  125 A  150 A  200 A
 Overload protection is   Thermal overload relay  Rated operational voltage U , 208...600 V AC
 used to protect the motor                               e
 from over heating  1)  TF42DU  TA75DU  TA110DU  Rated control supply voltage, U , 24 V AC/DC, 50/60 Hz
                                                           s
                                    0.75  1.5  2.2  3.9  0.5  0.75  2  2  3.4  PSR3-600-11  1SFA896103R1100  0.45  (0.99)
                                    1.5  3   4    6.8  1   1.5  3   5    6.1  PSR6-600-11  1SFA896104R1100  0.45  (0.99)
 The line contactor is not   Line contactor  2.2  4  4  9  2  2  5  7.5  9    PSR9-600-11  1SFA896105R1100  0.45  (0.99)
 required for the softstarter       3    5.5  5.5  12  3   3    7.5  10  11   PSR12-600-11  1SFA896106R1100  0.45  (0.99)
 itself but often used to   AF9  AF12  AF16  AF26  AF30  AF38  AF52  AF65  AF80  AF96  AF116
 open if OL trips   1)              4    7.5  7.5  16  3   5    10  10   15.2  PSR16-600-11  1SFA896107R1100  0.45  (0.99)
                                    5.5  11  15   25   7.5  7.5  15  20  24.2  PSR25-600-11  1SFA896108R1100  0.65  (1.43)
                                    7.5  15  18.5  30  7.5  10  20  25   28   PSR30-600-11  1SFA896109R1100  0.65  (1.43)
                                    7.5  18.5  22  37  10  10   25  30   34   PSR37-600-11  1SFA896110R1100  1.00  (2.20)
                                    11   22  30   45   15  15   30  40   46.2  PSR45-600-11  1SFA896111R1100  1.00  (2.20)
                                    15   30  37   60   20  20   40  50   59.4  PSR60-600-11  1SFA896112R1100  2.20  (4.85)
                                    22   37  45   72   20  25   50  60   68   PSR72-600-11  1SFA896113R1100  2.27  (5.00)
                                    22   45  55   85   25  30   60  75   80   PSR85-600-11  1SFA896114R1100  2.27  (5.00)
                                    30   55  55   105  30  40   75  100  104  PSR105-600-11 1SFA896115R1100  2.27  (5.00)
 2/4    1SFC132012C0201 - Rev. B | Softstarter Catalog                         Softstarter Catalog | 1SFC132012C0201 - Rev. B |    2/5
   14   15   16   17   18   19   20   21   22   23   24