Page 19 - Catalog Softstarters PSR PSE PSTX
P. 19
PSR – The compact range
Ordering details
Description
Selection table for normal start. Typical applications:
– Bow thruster
– Centrifugal pump
1SFC132020V0001 – Compressor 2
– Conveyor belt (short)
– Elevator
PSR3 ... PSR16 For a more precise selection, use the online softstarter selection tool available by scanning the shown QR
code or using the selection tool available on:
new.abb.com/low-voltage/products/softstarters
1SFC132072V0001 Rated operational voltage U , 208...600 V AC
e
s
Normal start PSR3 PSR6 PSR9 PSR12 PSR16 PSR25 PSR30 PSR37 PSR45 PSR60 PSR72 PSR85 PSR105 Rated control supply voltage, U , 100...240 V AC, 50/60 Hz Type Order code Weight
IEC
UL/CSA
In-line connected PSR25 ... PSR30
(400 V) kW 1.5 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 Rated operational Rated operational pkg
IEC, max. A 3.9 6.8 9 12 16 25 30 37 45 60 72 85 105 power 400 V 500 V current power current (1 pce)
230 V
200 / 220 / 440 / 550 /
(440-480 V) hp 2 3 5 7.5 10 15 20 25 30 40 50 60 75 208 V 240 V 480 V 600 V
UL, max. FLA 3.4 6.1 9 11 15.2 24.2 28 34 46.2 59.4 68 80 104 P e P e P e I e P e P e P e P e FLA
400 V, 40 ºC 1SFC132024V0001 kW kW kW A hp hp hp hp A kg (lb)
Using manual motor Manual motor starter (50 kA) 0.75 1.5 2.2 3.9 0.5 0.75 2 2 3.4 PSR3-600-70 1SFA896103R7000 0.45 (0.99)
starters type 1 coordina- 1.5 3 4 6.8 1 1.5 3 5 6.1 PSR6-600-70 1SFA896104R7000 0.45 (0.99)
tion will be achieved 1) MS116 MS132 MS450 MS495 — PSR37 ... PSR45 2.2 4 4 9 2 2 5 7.5 9 PSR9-600-70 1SFA896105R7000 0.45 (0.99)
3 5.5 5.5 12 3 3 7.5 10 11 PSR12-600-70 1SFA896106R7000 0.45 (0.99)
Using gG fuses type 1 Fuse protection (50 kA) gG Fuse 4 7.5 7.5 16 3 5 10 10 15.2 PSR16-600-70 1SFA896107R7000 0.45 (0.99)
coordination will be 5.5 11 15 25 7.5 7.5 15 20 24.2 PSR25-600-70 1SFA896108R7000 0.65 (1.43)
achieved 1) 10 A 16 A 25 A 32 A 50 A 63 A 100 A 125 A 200 A 250 A 7.5 15 18.5 30 7.5 10 20 25 28 PSR30-600-70 1SFA896109R7000 0.65 (1.43)
PSR37-600-70
34
30
25
10
10
37
18.5
22
7.5
1.00
(2.20)
1SFA896110R7000
Suitable switch fuse for the Switch fuse 1SFC132028V0001 11 22 30 45 15 15 30 40 46.2 PSR45-600-70 1SFA896111R7000 1.00 (2.20)
above gG fuses 1) OS32G OS125G OS250 15 30 37 60 20 20 40 50 59.4 PSR60-600-70 1SFA896112R7000 2.20 (4.85)
45
72
1SFA896113R7000
25
(5.00)
2.27
20
37
50
22
60
PSR72-600-70
68
22 45 55 85 25 30 60 75 80 PSR85-600-70 1SFA896114R7000 2.27 (5.00)
J-type fuses for UL Max. fuse, J-type PSR60 ... PSR105 30 55 55 105 30 40 75 100 104 PSR105-600-70 1SFA896115R7000 2.27 (5.00)
coordination 1) 35 A 60 A 90 A 110 A 125 A 150 A 200 A
Overload protection is Thermal overload relay Rated operational voltage U , 208...600 V AC
used to protect the motor e
from over heating 1) TF42DU TA75DU TA110DU Rated control supply voltage, U , 24 V AC/DC, 50/60 Hz
s
0.75 1.5 2.2 3.9 0.5 0.75 2 2 3.4 PSR3-600-11 1SFA896103R1100 0.45 (0.99)
1.5 3 4 6.8 1 1.5 3 5 6.1 PSR6-600-11 1SFA896104R1100 0.45 (0.99)
The line contactor is not Line contactor 2.2 4 4 9 2 2 5 7.5 9 PSR9-600-11 1SFA896105R1100 0.45 (0.99)
required for the softstarter 3 5.5 5.5 12 3 3 7.5 10 11 PSR12-600-11 1SFA896106R1100 0.45 (0.99)
itself but often used to AF9 AF12 AF16 AF26 AF30 AF38 AF52 AF65 AF80 AF96 AF116
open if OL trips 1) 4 7.5 7.5 16 3 5 10 10 15.2 PSR16-600-11 1SFA896107R1100 0.45 (0.99)
5.5 11 15 25 7.5 7.5 15 20 24.2 PSR25-600-11 1SFA896108R1100 0.65 (1.43)
7.5 15 18.5 30 7.5 10 20 25 28 PSR30-600-11 1SFA896109R1100 0.65 (1.43)
7.5 18.5 22 37 10 10 25 30 34 PSR37-600-11 1SFA896110R1100 1.00 (2.20)
11 22 30 45 15 15 30 40 46.2 PSR45-600-11 1SFA896111R1100 1.00 (2.20)
15 30 37 60 20 20 40 50 59.4 PSR60-600-11 1SFA896112R1100 2.20 (4.85)
22 37 45 72 20 25 50 60 68 PSR72-600-11 1SFA896113R1100 2.27 (5.00)
22 45 55 85 25 30 60 75 80 PSR85-600-11 1SFA896114R1100 2.27 (5.00)
30 55 55 105 30 40 75 100 104 PSR105-600-11 1SFA896115R1100 2.27 (5.00)
2/4 1SFC132012C0201 - Rev. B | Softstarter Catalog Softstarter Catalog | 1SFC132012C0201 - Rev. B | 2/5