Page 194 - Motor_protection_and_control_Manual_motor_starters_ contactors
P. 194

Surge suppressors for contactor coils








                                  Description
                       (V)
                     1000
                                  The operation of inductive circuits causes overvoltages, in particular on opening the contactor coil.
                          T (µs)
                      0  100      The electromagnetic energy stored in the coil during contactor closing is restored on opening in the form
                                  of surges, the slope and amplitude of which may rise to several kilovolts. A number of drawbacks are
       1000
                                  observed ranging from interference on the electronic devices to the breakdown of insulators and even the
         0  100                   destruction of certain sensitive components.
                                  The graph opposite reproduces the oscillogram showing voltage discharges at the terminals of a 42 V / 50 Hz
                                  coil without peak clipping. The coil was switched by 8 series-connected poles of a contactor relay.
                                  Following a burst of discharges with a very steep slope, a damped oscillation emerges with a peak value
                                  of 3500 V.
    4                             Overvoltage Factor
                                  The overvoltage factor k is defined as the ratio of the maximum overvoltage peak value Ûs to the peak
                                  value Ûc of the coil rated control voltage Uc:
                                      Ûs max.                         Ûs max.                   Ûs max.
                                   k =                       in DC  k =                in AC  k =
                                        Ûc                             Uc                        Uc √2
               1SBC101042F0014    For example the following is obtained for the above graph:     k =   42 √2   ≈ 60
                                                                                         3500

                                  signed to reduce the k factor defined above and to limit or even completely eliminate the high pre-damping
       RV5                        To reduce the harmful effects of these overvoltages, ABB has developed a range of surge suppressors de-
                                  voltage frequencies.
                                  Each case is different, but the technical data tolerances and generous sizing of parts have enabled us to
                                  reduce the number of variants.
                                  We have chosen the following solutions: transil diodes, varistors and RC blocks.
                                  Note: A varistor is a resistor whose value decreases to a very large extent when a certain voltage is ap-
                                  plied at its terminals.
               1SBC101042F0014    Ordering details



                                           contactor
                                                                                                      qty
                                                                                                           (1 pce)
                                  contactors
                                                        voltage - Uc
       RC5-1                      For      For          Rated control circuit    Type   Order code    Pkg   Weight
                                           relays       V        AC  DC                                    kg
                                  AS, ASL  NS, NSL      24...50   ●  ●  RV5/50     1SBN050010R1000     2   0.015
                                                        50...133  ●  ●  RV5/133    1SBN050010R1001     2   0.015
                                                        110...250  ●  ●  RV5/250   1SBN050010R1002     2   0.015
                                                        250...440  ●  ●  RV5/440   1SBN050010R1003     2   0.015
                                  AS       NS           24...50   ●  – –  RC5-1/50  1SBN050100R1000    2 2  0.012
                                                        50...133
                                                                        RC5-1/133
                                                                                                           0.012
                                                                                   1SBN050100R1001
                                                                  ●
               1SBC101042F0014    ASL      NSL          110...250  ●  ●  RC5-1/250  1SBN050100R1002    2 2 2  0.012
                                                                     –
                                                        250...440
                                                                     –
                                                                                                           0.012
                                                                                   1SBN050100R1003
                                                                        RC5-1/440
                                                                  ●
                                                                                   1SBN050020R1000
                                                                                                           0.015
                                                                        RT5/32
                                                                  –
                                                        12...32
       RT5                                              25...65   –  ●  RT5/65     1SBN050020R1001     2   0.015
                                                        50...90   –  ●  RT5/90     1SBN050020R1002     2   0.015
                                                        77...150  –  ●  RT5/150    1SBN050020R1003     2   0.015
                                                        150...264  –  ●  RT5/264   1SBN050020R1004     2   0.015
                                  Main dimensions mm, inches
                                       72.5  2.85"          45  1.77"        45  1.77"
                                                                               Easy connection to the coil terminals
                                                                               (parallel mounting)
                                                                               Clip-on for both fixing and connection.
                                                       68  2.68"        68  2.68"  No additional space
                                                                               Clipped onto the right side part of
                                                                               the contactor base without changing
                                                                               contactor overall dimensions and   1SBC101494S0201
                                                                               keeping a free access to coil terminals.