AF50 … AF95B  3-pole contactors

         Technical data





         General technical data
         Contactor types                               AF50           AF63           AF75           AF95B
         Rated insulation voltage Ui
           acc. to IEC 60947-4-1                       1000 V
           acc. to UL                                  600 V                                                        2
         Rated impulse withstand voltage Uimp.         8 kV
         Electromagnetic compatibility                 Devices complying with IEC 60947-1 / EN 60947-1 - Environment A
         Ambient air temperature close to contactor
           Operation  Fitted with thermal overload relay  -25...+55 °C
                     Without thermal overload relay    -40…+70 °C
           Storage                                     -60...+80 °C                                 -40...+70 °C
         Climatic withstand                            acc. to IEC 60068-2-30 and 60068-2-11        acc. to IEC 60068-2-30
                                                       UTE C 63-100 specification II
         Maximum operating altitude (without derating)  3000 m
         Mechanical durability
           Number of operating cycles                  10 millions operating cycles
           Max. switching frequency                    300 cycles/h
         Shock and vibration withstand                 Category 1, class B                          IEC 61373: 1999
         acc. to IEC 61373                                                                          (tables 2 and 3,
                                                                                                    category 1)


         Magnet system characteristics
         Contactor types                               AF50           AF63           AF75           AF95B
         Coil operating limits             AC or DC supply At θ ≤ 70 °C 0.85 x Uc min...1.1 x Uc max.
         acc. to IEC 60947-4-1
         DC control voltage
           Rated control circuit voltage Uc            20…250 V DC
           Coil consumption             Average pull-in value 190 W                                 400 W
                                        Average holding value 2.8 W                                 2 W
         AC control voltage 50/60 Hz
           Rated control circuit voltage Uc            48…250 V 50/60 Hz
           Coil consumption             Average pull-in value 210 VA                                350 VA
                                        Average holding value 7 VA / 2.8 W                          7 VA / 3.5 W
           Max. permitted control voltage              Rated control circuit voltage / Max. permitted control voltage
           during voltage fluctuation defined          48 ... 130 V AC 50/60 Hz / 150 V AC 50/60 Hz
           acc. to IEC 60077 / EN 50155                100 ... 250 V AC 50/60 Hz / 275 V AC 50/60 Hz
         Drop-out voltage                              55 % of Uc min.
         Operating time
           Between coil energization and:  N.O. contact closing 30…100 ms                           30…80 ms
                                        N.C. contact opening 27…95 ms                               27…77 ms
           Between coil de-energization and:  N.O. contact opening 30…110 ms                        55…125 ms
                                         N.C. contact closing 35…115 ms                             60…130 ms

         Mounting characteristics and conditions for use
         Contactor types                               AF50           AF63           AF75           AF95B
         Mounting positions        Pos. 2    +30°  -30°    Pos. 2   +30°  -30°

                               Pos. 4                  Pos. 4
                                       Pos. 3                  Pos. 3

                                     Pos. 1     Pos. 1 ± 30°  Pos. 5  Pos. 6        Pos. 5    Pos. 6
                                                             Pos. 1
                                                                        Pos. 1 ± 30°
                                                       Pos. 1 ± 30°, pos. 5: please consult us.
                                                       Max. built-in and add-on N.O. or N.C. auxiliary contacts:
                                                       see accessory fitting details for 3-pole contactor AF50 ... AF95B
         Mounting distances                            The contactors can be assembled side by side
         Fixing                                                                                     –
                  On rail according to IEC 60715, EN 60715  35 x 15 mm or 75 x 25 mm
                  By screws (not supplied)             2 x M6 screws placed diagonally