Page 492 - Residentiel
P. 492
MCB - Ph/N @ 230/240 V Coordination des protections
Sélectivité
Amont 2 S800 N-S S800 N-S S800 N-S
8
Aval 1 Courbe
8/26 | ABB Résidentiel et petit tertiaire
BCD
Icu [kA] 36-50 36-50 36-50
6
10 In [A] 25 32 40 50 63 80 100 125 25 32 40 50 63 80 100 125 25 32 40 50 63 80 100 125
2 0.6 1.3 4 T T T 0.55 1.2 3 T T T T 1.3 4.1 T T T T T T
4 0.45 0.8 1.5 2.5 4 T
6 0.43 0.75 1.3 2.1 3.9 T T 0.8 1.6 3 5.4 T T T T
10 0.6 1.2 1.6 2.6 3.8
16 0.5 1.1 1.4 2 3 0.55 1.1 1.5 2.5 3.6 5.5 0.6 1.3 2 3.2 3.9 T T T
20
SN201L 25 0.8 1.2 1.7 2.5 0.45 1 1.3 1.9 2.8 4.2 0.5 1.2 1.65 2.6 3.1 T T T
DS201L 32 1 1.5 2.1
C 40 1.3 1.8 0.75 1.1 1.6 2.3 3.6 0.9 1.4 1.8 2.6 5 T T
SN201 C, D 2 1.1 1.7
DS201 4 1.6 0.9 1.4 1.9 3.3 1.3 1.6 2.2 4.2 5.4 T
6
10 0.6 1.3 4 9 T T 1.2 1.6 2.7 1.5 1.9 3.5 4.5 T
16 0.45 0.8 1.5 2.5 4 7.3
20 1 1.5 2.5 1.8 2.8 4.2 5.5
25 0.6 1.2 1.6 2.6 3.8
32 0.5 1.1 1.4 2 3 1.4 2.1 1.7 2.7 4 5
40
0.8 1.2 1.7 2.5 0.55 1.2 3 6.6 T T T 1.3 4.1 T T T T T T
1 1.5 2.1
1.3 1.8 0.43 0.75 1.3 2.1 3.9 6.6 T 0.8 1.6 3 5.4 7.6 T T T
1.1 1.7
1.6 0.55 1.1 1.5 2.5 3.6 5.5 0.6 1.3 2 3.2 3.9 8 T T
0.45 1 1.3 1.9 2.8 4.2 0.5 1.2 1.65 2.6 3.1 6.2 8.6 T
0.75 1.1 1.6 2.3 3.6 0.9 1.4 1.8 2.6 5 6.3 8.8
0.9 1.4 1.9 3.3 1.3 1.6 2.2 4.2 5.4 7.6
1.2 1.6 2.7 1.5 1.9 3.5 4.5 6.6
1 1.5 2.5 1.8 2.8 4.2 5.5
1.4 2.1 1.7 2.7 4 5
1 Disjoncteur Aval 1P+N (230/240 V)
2 Pour réseau 230/240 V AC ➞ disjoncteur bipolaire (phase + neutre)
Pour réseau 400/415 V AC ➞ disjoncteur tétrapolaire (disjoncteur aval entre phase et neutre)