Page 505 - Motor_protection_and_control_Manual_motor_starters_ contactors
P. 505

Control of three-phase slip-ring motors

         Contactor selection




         Example of a three-stroke starter
            – The first stroke corresponds to energization of the motor by the sta-  Rotor short-circuit  Acceleration
           tor contactor: all the resistances are operational in the rotor circuit  Stator   contactor   contactor
            – At the second stroke, the acceleration contactor short-circuits the   contactor
           first resistance stack
            – At the third stroke, the rotor short-circuit contactor is
           activated by eliminating the last resistance stack, thus completing             R2               R1
           the starting period.                                       M
                                                                      3







                                                                                                                    5

         Contactor types             AF116 AF140 AF190 AF205 AF265 AF305 AF370  AF400  AF460  AF580  AF750  AF1350 AF1650
         Load factor  15 %   Ie  / AC-2    A   220  335  360  425  530  625  750  850  950  1150  1500  1720  2100
                  25 %      Ie  / AC-2    A   185  270  300  350  440  515  620  680  780  975  1250  1430  1750
                  40 %      Ie  / AC-2    A   150  215  250  300  370  430  515  580  650  800  1050  1200  1470
                  60 %      Ie  / AC-2    A   135  180  220  255  315  370  430  480  550  700  900   1030  1250
         S7 acc. to IEC 60034-1: periodical     A   116  140  190  210  265  305  370  400  460  580  750  860  1050
         continuous duty with electrical breaking





















         Contactors                  AF116 AF140 AF190 AF205 AF265 AF305 AF370  AF400  AF460  AF580  AF750  AF1350 AF1650
         Rated operational current Ie / AC-1   A   145  175  250  300  350  400  500  500  600  700  800  1150  1450
         for air temperature near the contactor
         ≤ 60 °C (AF116-AF370)  ≤ 55 °C
         (AF400-AF1650)








         Contactor types             AF116 AF140 AF190 AF205 AF265 AF305 AF370  AF400  AF460  AF580  AF750  AF1350 AF1650
         Load factor  15 %   Ie       A   330  540  580  750  830  950  1050  1200  1400  1650  1900  2400  2800
                  25 %      Ie       A   300  490  530  650  725  830  915   1050  1250   1450  1650  2100  2500
                  40 %      Ie     A   260  425  460  575   630  720   800   950   1100   1300  1450  1850  2200
                  60 %      Ie      A   230  375  400  500  575  650   700   810   975    1150  1300  1650  1950
         S7 acc. to IEC 60034-1: periodical   A 200  300  350  380  480  550  640  700  840  980  1150  1500  1800
         continuous duty with electrical breaking
         Rated operational rotor voltage:
         –  Maximum values for starting and  V 2200         3000
          breaking                   (2600 in star connection)  (3600 in star connection)
         –  Maximum values for starting and  V 690                                                                  1SBC101969S0201 - Rev. B
          electrical braking         (730 in star connection)



                                                                                                         ABB  |  5/305