Page 756 - Motor_protection_and_control_Manual_motor_starters_ contactors
P. 756

EF460, EF750 electronic overload relays – 150 to 800 A

       Technical data





       Main circuit – Utilization characteristics according to IEC/EN
       Type                                         EF460                          EF750
       Standards                                    IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1
       Rated operational voltage U e                1000 V AC
       Rated frequency                              50/60 Hz – not suitable for DC applications
       Trip class                                   10E, 20E, 30E, selectable
       Number of poles                              3
       Duty time                                    100%
       Operating frequency without early tripping   Up to 15 operations/h, see "Technical diagram – Intermittent periodic duty"
       Rated impulse withstand voltage U imp        8 kV
       Rated insulation voltage U                   1000 V AC
                      i
       Auxiliary circuit according to IEC/EN
       Type                                         EF460                          EF750
       Rated operational voltage U e                600 V AC / DC
       Conventional free air thermal current I th   6 A
       Rated frequency                              DC, 50/60 Hz
       Number of poles                              1 N.C. + 1 N.O.
       I  / Rated operational current AC-15
       e
       acc. to IEC/EN 60947-5-1 for utilization category
                110-120 V                     50/60 Hz 3.00 A
    7           220-230-240 V                 50/60 Hz 3.00 A
                400 V                         50/60 Hz 1.10 A
                480-500 V                     50/60 Hz 0.75 A
       I  / Rated operational current DC-13
       e
       acc. to IEC/EN 60947-5-1 for utilization category
                24 V                                1.50 A
                60 V                                0.55 A
                110-120-125 V                       0.55 A
                250 V                               0.27 A
       Minimum switching capacity                   12 V / 3 mA
       Short-circuit protective device              6 A, fuse type gG
       Rated impulse withstand voltage U imp        6 kV
       Rated insulation voltage U i                 690 V

       Technical diagram – Intermittent periodic duty
        (Op/h)  Trip class 10E    (Op/h)   Trip class 20E   (Op/h)   Trip class 30E
                                                             50
            a
        160   t   = 0.5 s                                        a
                                   80                        45   t   = 5 s
                                       a
        140                        70   t   = 2 s            40
        switching frequency      100   t   = 1 s  switching frequency      50   t   = 4 s  switching frequency      30   t   = 10 s
        120
                                                             35
                                   60
                                                             25
            a
         80
                                   40
                                                                 a
                                         a
                                                             20
         60
                                   30
            a
            t   = 1.5 s
                                          a
         40
                                                                  a
                                       a
                                                             10
            a
            t   = 3 s              20   a  t   = 8 s t   = 6 s  15   t   = 15 s
                                                                 a
         20                        10   t   = 10 s               t   = 20 s
            a
            t   = 5 s                 t   = 12 s              5   t   = 25 s
                                      a
                                                                a
         0                   2CDC232001F0214  0         2CDC232002F0214           2CDC232003F0214
          0   20  40  60  80  100   (%)  0   20  40  60  80  100   (%)  0  0   20  40  60  80  100   (%)
              duty ratio                 duty ratio                duty ratio
       Trip class 10E            Trip class 20E            Trip class 30E
                                                                                                                  2CDC107045C0201
       7/42  |  ABB
   751   752   753   754   755   756   757   758   759   760   761