Page 147 - Motor protection and control Manual motor starters, contactors and overload relays
P. 147

ABB  MOTOR PROTECTION AND CONTROL                                                3/73

          —

          AF09 ... AF96  3-pole contactors
          Technical data




          Built-in auxiliary contacts according to IEC                                                                03
          Contactor types          AC / DC operated AF09  AF12  AF16  AF26  AF30  AF38  AF40  AF52  AF65  AF80  AF96
          Rated operational voltage Ue max.   690 V
          Rated frequency (without derating)  50 / 60 Hz
          Conventional free air thermal current Ith - θ ≤ 40 °C  16 A
          Ie / Rated operational current AC-15
          acc. to IEC 60947-5-1   24-127 V 50/60 Hz 6 A
                                  220-240 V 50/60 Hz 4 A
                                 400-440 V 50/60 Hz 3 A
                                    500 V 50/60 Hz 2 A
                                    690 V 50/60 Hz 2 A
          Making capacity AC-15               10 x Ie AC-15 acc. to IEC 60947-5-1
          Breaking capacity AC-15             10 x Ie AC-15 acc. to IEC 60947-5-1
          Ie / Rated operational current DC-13
          acc. to IEC 60947-5-1         24 V DC 6 A / 144 W
                                        48 V DC 2.8 A / 134 W
                                        72 V DC 1 A / 72 W
                                        110 V DC 0.55 A / 60 W
                                        125 V DC 0.55 A / 69 W
                                        220 V DC 0.27 A / 60 W
                                       250 V DC 0.27 A / 68 W
                                       400 V DC 0.15 A / 60 W
                                       500 V DC 0.13 A / 65 W
                                       600 V DC 0.1 A / 60 W
          Short-circuit protection device gG type fuse  10 A
          Conditional short-circuit current   1 kA
          Rated short-time withstand current Icw  for 1.0 s 100 A
                                        for 0.1 s 140 A
          Minimum switching capacity          12 V / 3 mA
          with failure rate acc. to IEC 60947-5-4  10 -7
          Non-overlapping time between N.O. and N.C. contacts  ≥ 2 ms
          Power dissipation per pole at 6 A   0.1 W
          Max. electrical switching frequency  AC-15 1200 cycles/h
                                         DC-13 900 cycles/h
          Mechanically linked contacts        Built-in N.O. or N.C. auxiliary contacts and additional N.O. or N.C. auxiliary contacts (CA4, CAL4, CAT4 aux. contact blocks)
          acc. to annex L of IEC 60947-5-1    are mechanically linked contacts.
          Mirror contacts                     Built-in N.C. auxiliary contacts or additional N.C. auxiliary contacts (CA4, CAL4, CAT4 aux. contact blocks) are mirror
          acc. to annex F of IEC 60947-4-1    contacts.


          Built-in auxiliary contacts according to UL / CSA
          Contactor types         AC / DC operated AF09  AF12  AF16  AF26  AF30  AF38  AF40  AF52  AF65  AF80  AF96
          Max. operational voltage           600 V AC, 600 V DC
          Pilot duty                         A600, Q600
            AC thermal rated current         10 A
            AC maximum volt-ampere making    7200 VA
            AC maximum volt-ampere breaking  720 VA
            DC thermal rated current         2.5 A
            DC maximum volt-ampere making-breaking  69 VA

















                                                                                                                 1SBC101445S0201 - Rev. B