3/76             ABB  MOTOR PROTECTION AND CONTROL

          —

          3-pole contactors
          Electrical durability





          Electrical durability for AC-3 utilization category - Ue ≤ 440 V.
   03
          Switching cage motors: starting and switching off running motors. The breaking current Ic for AC-3 is equal to the rated
          operational current Ie (Ie = motor full load current).
          Ambient temperature and maximum electrical switching frequency: see "Technical data".




          Millions of                                                                            AF1350, AF1650:
                                                                                                 The electrical durability
          operating              AF30, AF38      AF80, AF96  AF140, AF146                        at the rated current is
                                                                                    AF750
          cycles  AF09  AF12  AF16  AF26  AF40  AF52  AF65  AF116  AF190 AF205 AF265 AF305 AF370  AF400 AF460  AF580*       *  50000 operating cycles.
           10

            5


            3        9
                     7
                     5
                     3
            2   9    1
          1.8   7
                5
                3
                1
            1

          0.5

              13 57 9                          13 57 9     15 9                13 57 9
          0.3
                                                                                    13 57 9
                                     1  3  5  7  9      15 9          1  3  5  7  9
          0.2
              2    3      5         10       20    30     50        100      200  300     500      1000
                                                           55
                                                                                                  Breaking current Ic (A)
          Note: * For AF580 and AF750 contacts needs to be replaced after 750k operations.
          Example:
          Motor power 30 kW for AC-3 - Ue = 400 V and Ie = 55 A utilization – Electrical durability required = 1.8 million operating cycles.
          For AC-3: Ic = Ie. Select the AF65 contactor at intersection " " (55 A / 1.8 million operating cycles) on the curves
          (AC-3 - Ue ≤ 440 V).