Page 304 - Motor protection and control Manual motor starters, contactors and overload relays
P. 304

3/230            ABB  MOTOR PROTECTION AND CONTROL

          —

          UA16 … UA110  3-pole contactors for capacitor switching
          Peak current Î ≤ 100 times the rms current
          Technical data



          Main pole - Utilization characteristics according to IEC
   03
          Contactor types           AC operated UA16  UA26   UA30     UA50    UA63     UA75    UA95     UA110
          Standards                         IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
          Rated operational voltage Ue max.  690 V
          Rated frequency (without derating)  50 / 60 Hz
          AC-6b Utilization category
            Rated operational power AC-6b (1)
            For air temperature close   θ ≤ 40 °C  230-240 V 7.5 kvar  12 kvar  16 kvar  20 kvar  25 kvar  30 kvar  35 kvar  40 kvar
            to contactor             400-415 V 12.5 kvar  20 kvar  27.5 kvar  33 kvar  45 kvar  50 kvar  65 kvar  75 kvar
                                        440 V 13.7 kvar  22 kvar  30 kvar  36 kvar  50 kvar  55 kvar  65 kvar  75 kvar
                                     500-550 V 15.5 kvar  22 kvar  34 kvar  40 kvar  50 kvar  62 kvar  70 kvar  80 kvar
                                        690 V 21.5 kvar  30 kvar  45 kvar  55 kvar  70 kvar  75 kvar  80 kvar  90 kvar
                             θ ≤ 55 °C  230-240 V 6.7 kvar  11 kvar  16 kvar  20 kvar  25 kvar  30 kvar  35 kvar  40 kvar
                                     400-415 V 11.7 kvar  18.5 kvar  27.5 kvar  33 kvar  43 kvar  50 kvar  65 kvar  70 kvar
                                        440 V 13 kvar  20 kvar  30 kvar  36 kvar  48 kvar  53 kvar  65 kvar  75 kvar
                                     500-550 V 14.7 kvar  22 kvar  34 kvar  40 kvar  50 kvar  62 kvar  70 kvar  80 kvar
            Multi-step capacitor        690 V 20 kvar  30 kvar  45 kvar  55 kvar  70 kvar  75 kvar  80 kvar  90 kvar
            bank scheme     θ ≤ 70 °C  230-240 V 6 kvar  8.5 kvar  11 kvar  19 kvar  21 kvar  22 kvar  30 kvar  35 kvar
                                     400-415 V 10 kvar  14.5 kvar  19 kvar  32 kvar  37 kvar  39 kvar  55 kvar  65 kvar
                                        440 V 11 kvar  16 kvar  20 kvar  35 kvar  41 kvar  43 kvar  55 kvar  70 kvar
                                     500-550 V 12.5 kvar  19.5 kvar  23.5 kvar  40 kvar  45 kvar  47.5 kvar  60 kvar  75 kvar
                                        690 V 17 kvar  25 kvar  32 kvar  52 kvar  60 kvar  65 kvar  70 kvar  85 kvar
          Max. permissible peak current Î  Ue ≤ 500 V 1.8 kA  3 kA  3.5 kA  5 kA  6.5 kA  7.5 kA  9.3 kA  10.5 kA
                                     Ue > 500 V 1.6 kA  2.7 kA  3.1 kA  4.5 kA  5.8 kA  6.75 kA  8 kA   9 kA
          Short-circuit protection device for contactors
          gG type fuse                      sized 1.5…1.8 In of the capacitor
          Max. electrical switching frequency  240 cycles/h
          Electrical durability AC-6b  Ue ≤ 690 V 100 000 operating cycles
          (1) For 220 V and 380 V, multiply by 0.9 the rated values at 230 V and 400 V respectively.
          Example: 50 kvar / 400 V corresponding to 0.9 x 50 = 45 kvar/380 V.
          If, in an application, the current peak is greater than the maximum peak current Î specified in the tables above, select a higher rating, refer to the UA..RA contactors, or add induc-
          tances. (see application guide "Contactors for capacitor switching").
          Main pole - Utilization characteristics according to UL / CSA
          Contactor types           AC operated UA16  UA26   UA30     UA50    UA63     UA75    UA95     UA110
            Power - 60 Hz
            For air temperature close   θ ≤ 40 °C  240 V -  12.5 kvar  16 kvar  20 kvar  -  27.5 kvar  35 kvar  40 kvar
            to contactor                480 V -      25 kvar  32 kvar  40 kvar  -      55 kvar  70 kvar  80 kvar
                                        600 V -      30 kvar  40 kvar  50 kvar  -      70 kvar  75 kvar  85 kvar
          If, in an application, the current peak is greater than the maximum peak current Î specified in the tables above, select a higher rating, refer to the UA..RA contactors, or add induc-
          tances. (see application guide "Contactors for capacitor switching").


























                                                                                                                 1SBC101536S0201