Page 69 - 1SBC104119C0202_MainCatalog_R contactors
P. 69

FORR1000SPE … FORR2100SPE and
FORE1000SPE … FORE2100SPE contactors
Rotor voltages up to 4200 V AC

Main pole - Utilization characteristics according to IEC (Y only connection diagram)

Contactor types                          AC operated FORR1000SPE FORR1400SPE FORR1700SPE FORR2100SPE FORR2500SPE FORR3200SPE FORR3800SPE

                                         DC operated FORE1000SPE FORE1400SPE FORE1700SPE FORE2100SPE FORE2500SPE FORE3200SPE FORE3800SPE

Rated rotor operational voltage Uer                   4200 V

Rated frequency (without derating)                    0.1...60 Hz (for > 60 Hz consult us)

Conventional free-air thermal current Ith

acc. to IEC 60947-4-1, θ ≤ 40 °C                      1000 A        1400 A             1700 A    2100 A    2500 A    3200 A    3800 A
    With conductor cross-sectional area               600 mm²       1000 mm²           1500 mm²  2000 mm²  2000 mm²  3000 mm²  3000 mm²

Rated rotor operational current Ier

For air temperature close to contactor

                                           θ ≤ 40 °C  1000 A        1400 A             1700 A    2100 A    2500 A    3200 A    3800 A
                                           θ ≤ 55 °C  930 A         1180 A             1450 A    1750 A    2200 A    2800 A    3200 A
                                           θ ≤ 70 °C  800 A         1000 A             1250 A    1500 A    1830 A    2350 A    2780 A
                                                      600 mm²       1000 mm²           1500 mm²  2000 mm²  2000 mm²  3000 mm²  3000 mm²
With conductor cross-sectional area

Maximum making capacity                               14000 A       19000 A            21000 A   24000 A   24000 A   26000 A   29000 A

Maximum breaking capacity at                     1500 A             2100 A             2600 A    3200 A    3800 A    4800 A    5700 A                          5
                                           1 s 9000 A               11000 A            13000 A   15000 A   20000 A   21000 A   24000 A
cos φ = 0.80 and 1000 V
Rated short-time withstand current Icw

at 40 °C ambient temperature,              10 s 8000 A              9000 A             11000 A   12200 A   15000 A   18000 A   19000 A

in free air from a cold state              30 s 4000 A              5000 A             6000 A    7000 A    8000 A    10000 A   11000 A

                                           1 min 3000 A             3700 A             4400 A    5000 A    6000 A    7000 A    7500 A

                                           15 min 1600 A            2000 A             2400 A    2800 A    3000 A    4000 A    4500 A

Impedance per pole                                    0.18 mΩ       0.10 mΩ            0.09 mΩ   0.08 mΩ   0.05 mΩ   0.045 mΩ  0.04 mΩ

Maximum electrical switching frequency                120 cycles/h

Mechanical durability

Number of operating cycles                            5 millions    2 millions cycles
                                                      cycles

Max. switching frequency                              600 cycles/h

Note: - Uer > 4200 V AC, please consult us.
	 - Altitude ≥ 2000 m, dimension drawings: please consult us.

                                                                                                                                              1SBC104033S0201

                                                                                                                     ABB R contactors | 5/17