Page 27 - Kabeldon
P. 27

Switching devices with dependent manual operation

         SLD 1, 250 A












                                                                                                                    2








                                                                KSBD 2                     KN 1
                                                                Blocking device.           Linking knife.


















         SLD 1
         Fuse-switch-disconnector.
            − AC-23B according to
           IEC 60947-3 at 400 V.
            − 10 modules or 120 mm width.  JDDA 1              STM 400                 ADP 300
            − Fuse NH 1 (max width 42 mm) or   Earthing device for SLD 1.  Conductor rail with connector for   Insulated connector for parallel
           linking knife KN 1.                                 current transformer metering.  conductors with fuse-switch-disconnectors
                                                               Dimensions of conductor rail are   SLD 1, SLD 2 and also circuit-breakers
                                                               25x13 mm.               ABB Tmax T5.
         Note:
         Switching devices to be tightened with the torque.
         For “Tightening torque” see page 5/6.


          Designation  ID No.       Degree of protection  Number of   Rated data  Cable connection    Weight
                                                       modules                       Al/Cu
                                                        M *      400 V    690 V      mm²       kg/pcs
          SLD 1     2CGX0 63050108        IP2X           10      250 A **  250 A   50-300 ***    4.3
         * One module M = 12.5 mm.
         ** 250 A with fuse, 400 A with linking knife.
         *** Max. conductor cross section refers to connection with a stranded or solid conductor.

         To be ordered separately:
          Designation  ID No.       Degree of protection    Rated data  Dimensions  Cable connection   Numbers   Weight
                                                                                     Al/Cu      per kit
                                                                 H     B    D
                                                                      mm             mm²               kg/pcs
          JDDA 1    2CGX0 63190402        –           16.2 kA/1 s  –   –    –         –          1      0.4
          KSBD 2    2CGX0 63190110        –              –        –    –    –         –          3      0.1
          KN 1      2CGX0 53190345        –             400 A     –    –    –         –          3      0.2
          STM 400   2CGX0 63090026       IP2X         400 V, 400 A  220  35  85     50-300       1      0.4
          ADP 300   2CGX0 63090035       IP2X         690 V, 630 A  253  38  127   2//50-300     1      0,8



                                                             | Switching devices | Kabeldon fusegear and cable distribution cabinets | 2016 |  2/10