Page 28 - Kabeldon
P. 28

Switching devices with dependent manual operation

       SLD 2, 400 A












   2


                                                                   PHD 2                 PHD 2 SDC
                                                                   Parallel handle for parallel   Parallel handle for parallel operation
                                                                   operation of two SLD 2 in   of two SLD 2 in enclosures SDC
                                                                   enclosures CDC.       and CSS switchgears.












                                                                   KSBD 2                KNB 2
                                                                   Blocking device.      Linking knife.




       SLD 2                               JDDA 2
       Fuse-switch-disconnector            Earthing device.
          − AC-23B according to IEC 60947-3 at 400 V.
          − 12 modules or 150 mm width
          − Fuse NH 2 or linking knife KNB 2.
          − Possibility for parallel operation
          − Tested up to 1000 V for installation in dry
         indoor environments.
          − When using SLD 2 in 1000V systems, fuses
         that are designed for 1000 V must be used.
                                                                   STM 400              ADP 300
       Note:                                                       Conductor rail with connector  Insulated connector for parallel
       Switching devices to be tightened with the torque.          for current transformer    conductors with fuse-switch-
                                                                                        disconnectors SLD 1, SLD 2 and
       For “Tightening torque” see page 5/6.                       metering. Dimensions of    also circuit-breakers
                                                                   conductor rail are 25x13 mm.
                                                                                        ABB Tmax T5.
        Designation  ID No.       Degree of    Number of   Rated data when voltage level  Cable connection   Weight
                                  protection  modules   400 V   690 V   1000 V      Al/Cu
                                               M *                A                 mm²        kg/pcs
        SLD 2     2CGX0 63050109    IP2X        12      400 **   355     100       50-300 ***    4.6
       * One module M = 12.5 mm.
       ** 400 A with fuse, 630 A with linking knife.
       *** Max. conductor cross section refers to connection with a stranded or solid conductor.
       To be ordered separately:
        Designation  ID No.       Degree of     Rated data  Dimensions  Cable connection    Numbers   Weight
                                  protection            H     B    D        Al/Cu      per kit
                                                             mm             mm²                kg/pcs
        JDDA 2    2CGX0 63190401     –       16.2 kA/1 s  –   –    –         –           1      2.5
        PHD 2     2CGX0 63090024     –          –       –     –    –         –           1      1.5
        PHD 2 SDC  2CGX0 63090023    –          –       –     –    –         –           1      1.5
        KSBD 2    2CGX0 63190110     –          –       –     –    –         –           3      0.1
        KNB 2     2CGX0 53190321     –         630 A    –     –    –         –           3      0.2
        STM 400   2CGX0 63090026    IP2X     400 V, 400 A  220  35  85      50-300       1      0.4
        ADP 300   2CGX0 63090035    IP2X     690 V, 630 A  253  38  127    2//50-300     1      0,8

       2/11  | 2016 |  Kabeldon fusegear and cable distribution cabinets | Switching devices |