Page 30 - Kabeldon
P. 30

Switching devices with dependent manual operation, 630 A

       SLDL 2, SLDL 2-1P, SLDL 3, SLDL 3-1P








       The fuse-switch-disconnector available in four variants:
          − SLDL 2, 400 A for three-pole breaking.
          − SLDL 2-1P, 400 A for single-pole breaking.
   2      − SLDL 3, 630 A for three-pole breaking.
          − SLDL 3-1P, 630 A for single-pole breaking.

       Application area
       SLDL is used in the low voltage part of substations and
       similar applications.

       Standard
          − Meets the requirements of IEC 60947-3.
          − Degree of protection, IP2X.

       Design
       Fuse-switch-disconnectors’ outer layer is made of fiber
       glass reinforced plastic with strength according to the
       requirements for use in substations.
          − SLDL is 100 mm wide.                             SLDL 2, SLDL 3    SLDL 3-1P         SLDL 3
          − Fits to the Kabeldon busbar system.              Three-pole fuse-switch-  Single-pole fuse-switch-  Three-pole fuse-switch-
          − To enable cable connection from above, the rear section   disconnector for 400 A   disconnector for 630 A.  disconnector 630 A,
         of the apparatus can be reversed 180°. The handles’   and 630 A.                        mounted to connect the
         opening angle and direction are unchanged.                                              cable from above.
          − The design allows visual inspection of the screw
         connections’ mode after installation.
          − The cable may be connected in the apparatus with clamps
         or cable lugs.                                      NOTE:
          − Possibility for parallel operation of two SLDL.     − SLDL does not fit in the cable distribution cabinets
                                                               type CDC, SDC and KSIP.
       Suitable fuse sizes                                      − Terminal clamps must be ordered separately.
          − For SLDL 2 and SLDL 2-1P use NH2.                   − Switching devices to be tightened with torque.
          − For SLDL 3 and SLDL 3-1P use NH2, NH3.             For “Tightening torque” see page 5/6.





        Designation  ID No.       Degree of   Number of modules  Rated data  Cable connection   Weight
                                 protection                                   Al/Cu
                                                 M *          V      A         mm²       kg/pcs
        SLDL 2     2CGX0 63050242  IP 2X          8          400    400       35-240      5,5
                                                             690    400      2//95-240
                                                             1000   160
        SLDL 2-1P  2CGX0 63050243  IP 2X          8          230    400       35-240      5,3
                                                             400    400      2//95-240
                                                             690    160
        SLDL 3     2CGX0 63050240  IP 2X          8          400    630       35-240      6,4
                                                                             2//95-240
                                                             690    500
                                                             1000   160
        SLDL 3-1P  2CGX0 63050241  IP 2X          8          230    630       35-240      6,2
                                                             400    500      2//95-240
                                                             690    160
       * One module M = 12.5 mm.





       2/13  | 2016 |  Kabeldon fusegear and cable distribution cabinets | Switching devices |