Page 343 - Motor_protection_and_control_Manual_motor_starters_ contactors
P. 343

AF400 ... AF2650  3-pole contactors

         Technical data




         General technical data
         Contactor types            AC / DC operated AF400  AF460  AF580  AF750  AF1250  AF1350  AF1650  AF2050  AF2650
         Rated insulation voltage Ui
           acc. to IEC 60947-4-1               1000 V
           acc. to UL / CSA                    600 V                                1000 V
         Rated impulse withstand voltage Uimp.  8 kV
         Electromagnetic compatibility         AF contactors complying with IEC 60947-1 / EN 60947-1 - Environment A
         Ambient air temperature close to contactor
           Operation  Fitted with electronic overload relay  -25 to +70 °C
                     Without electronic overload relay  -40 to +70 °C
           Storage                             -40 to +70 °C
         Climatic withstand                    Category B according to IEC 60947-1 Annex Q
         Maximum operating altitude (without derating)  3000 m
         Mechanical durability
           Number of operating cycles          3 millions operating cycles  0.5 million operating cycles  0.3 million
                                                                                                         op. cycles
           Max. switching frequency            300 cycles/h                         60 cycles/h
         Shock withstand
         acc. to IEC 60068-2-27 and EN 60068-2-27                                                                   5
         Mounting position 1
                       C1            Shock direction 1/2 sinusoidal shock for 30 ms: no change in contact position, closed or open position
                                             A 5 g                                  –
            ABB                             B1 5 g                                  –
         A      A  B1      B2
                                            B2 5 g                                  –
                                            C1 5 g                                  –
                        C2                  C2 5 g                                  –
         Vibration withstand
         acc to IEC 60068-2-6                  0.7 g closed position / 0.7 g open position 13.2…100 Hz
         Magnet system characteristics
         Contactor types            AC / DC operated AF400  AF460  AF580  AF750  AF1250  AF1350  AF1650  AF2050  AF2650
         Coil operating limits          AC supply At θ ≤ 70 °C 0.85 x Uc min ... 1.1 x Uc max
         acc. to IEC 60947-4-1          DC supply At θ ≤ 70 °C 0.80 x Uc min ... 1.1 x Uc max
         Rated control circuit voltage Uc      48...500 V AC, 24...500 V DC         100...250 V AC or DC
           Coil consumption
             AC control voltage 50/60 Hz
             48...130 V AC        Average pull-in value 1215 VA  1100 VA            -
                                 Average holding value 12 VA  12 VA                 -
             100...250 V AC       Average pull-in value 955 VA  880 VA              2450 VA
                                 Average holding value 12 VA  12 VA                 48 VA
             250 … 500 V AC       Average pull-in value 950 VA  985 VA              -
                                 Average holding value 12 VA  12 VA                 -
             DC control voltage
             24...60 V DC         Average pull-in value 900 W  785 W                -
                                 Average holding value 5 W    5.5 W                 -
             48...130 V DC        Average pull-in value 1150 W  1020 W              -
                                 Average holding value 5 W    5 W                   -
             100...250 V DC       Average pull-in value 895 W  880 W                2290 W
                                 Average holding value 5 W    5 W                   20.5 W
             250 … 500 V DC       Average pull-in value 885 W  910 W                -
                                 Average holding value 7.5 W  7.5 W                 -
         Drop-out voltage                      55 % of Uc min.
         Voltage sag immunity                  Conditions of use on request
         acc. to SEMI F47
         Dips withstand                        ≥ 20 ms
         Operating time
           Coil supply between A1 - A2
           Between coil energization and:  Main contact closing 50…120 ms           50…80 ms
           Between coil de-energization and: Main contact opening 33…70 ms          35…55 ms
           Control input for PLC's
           Between coil energization and:  Main contact closing 40…60 ms  40...90 ms  40…65 ms
           Between coil de-energization and: Main contact opening 10…30 ms          10…30 ms
         Mounting characteristics and conditions for use
         Contactor types            AC / DC operated AF400  AF460  AF580  AF750  AF1250  AF1350  AF1650  AF2050  AF2650
         Mounting positions                        Pos. 2    +30°  -30°

                                               Pos. 4
                                                       Pos. 3
                                                     Pos. 1     Pos. 1 ± 30°  Pos. 5   Pos. 6
                                               Max. add-on N.O. or N.C. auxiliary contacts: see accessory fitting details for 3-pole contactor   1SFC101113C0201 - Rev. D
                                               AF400 ... AF2650                                                     1SFC101113C0201
         Mounting distances                    The contactors can be assembled side by side
         Fixing
           On rail according to IEC 60715, EN 60715  –
           By screws (not supplied)            4 x M5         4 x M6                 4 x M8
                                                                                                         ABB  |  5/143