Page 348 - Motor_protection_and_control_Manual_motor_starters_ contactors
P. 348

AF09 ... AF96  3-pole contactors

       Technical data





       Built-in auxiliary contacts according to IEC
       Contactor types                   AC / DC operated AF09  AF12  AF16  AF26  AF30  AF38  AF40  AF52  AF65  AF80  AF96
       Rated operational voltage Ue max.             690 V
       Rated frequency (without derating)            50 / 60 Hz
       Conventional free air thermal current Ith - θ ≤ 40 °C  16 A
       Ie / Rated operational current AC-15
       acc. to IEC 60947-5-1             24-127 V 50/60 Hz 6 A
                                        220-240 V 50/60 Hz 4 A
                                        400-440 V 50/60 Hz 3 A
                                           500 V 50/60 Hz 2 A
                                           690 V 50/60 Hz 2 A
       Making capacity AC-15                         10 x Ie AC-15 acc. to IEC 60947-5-1
       Breaking capacity AC-15                       10 x Ie AC-15 acc. to IEC 60947-5-1
       Ie / Rated operational current DC-13
       acc. to IEC 60947-5-1                   24 V DC 6 A / 144 W
    5                                          48 V DC 2.8 A / 134 W
                                               72 V DC 1 A / 72 W
                                              110 V DC 0.55 A / 60 W
                                              125 V DC 0.55 A / 69 W
                                              220 V DC 0.27 A / 60 W
                                              250 V DC 0.27 A / 68 W
                                              400 V DC 0.15 A / 60 W
                                              500 V DC 0.13 A / 65 W
                                              600 V DC 0.1 A / 60 W
       Short-circuit protection device gG type fuse  10 A
       Rated short-time withstand current Icw  for 1.0 s 100 A
                                               for 0.1 s 140 A
       Minimum switching capacity                    12 V / 3 mA
       with failure rate acc. to IEC 60947-5-4       10 -7
       Non-overlapping time between N.O. and N.C. contacts  ≥ 2 ms
       Power dissipation per pole at 6 A             0.1 W
       Max. electrical switching frequency      AC-15 1200 cycles/h
                                                DC-13 900 cycles/h
       Mechanically linked contacts                  Built-in N.O. or N.C. auxiliary contacts and additional N.O. or N.C. auxiliary contacts (CA4, CAL4, CAT4
       acc. to annex L of IEC 60947-5-1              aux. contact blocks) are mechanically linked contacts.
       Mirror contacts                               Built-in N.C. auxiliary contacts or additional N.C. auxiliary contacts (CA4, CAL4, CAT4 aux. contact blocks)
       acc. to annex F of IEC 60947-4-1              are mirror contacts.


       Built-in auxiliary contacts according to UL / CSA
       Contactor types                   AC / DC operated AF09  AF12  AF16  AF26  AF30  AF38  AF40  AF52  AF65  AF80  AF96
       Max. operational voltage                      600 V AC, 600 V DC
       Pilot duty                                    A600, Q600
          AC thermal rated current                   10 A
          AC maximum volt-ampere making              7200 VA
          AC maximum volt-ampere breaking            720 VA
          DC thermal rated current                   2.5 A
          DC maximum volt-ampere making-breaking     69 VA












                                                                                                                  1SBC101445S0201 - Rev. A








       5/148  |  ABB
   343   344   345   346   347   348   349   350   351   352   353