Page 350 - Motor_protection_and_control_Manual_motor_starters_ contactors
P. 350

3-pole contactors

       Electrical durability





       Electrical durability for AC-1 utilization category - Ue ≤ 690 V
       Switching non-inductive or slightly inductive loads. The breaking current Ic for AC-1 is equal to the rated operational current of
       the load.
       Ambient temperature and maximum electrical switching frequency: see "Technical data".

                                                                                                 AF1250, AF1350,
       Millions of                                                                               AF1650, AF2050:
       operating                   AF30, AF38  AF80, AF96                     AF400 AF460  AF580  AF750  The electrical durability at
       cycles   AF09  AF12  AF16  AF26  AF40  AF52  AF65  AF116  AF140  AF146 AF190  AF205 AF265 AF305 AF370  the rated current is 50000
                                                                                                 operating cycles.
       10



        5
    5

        3         9
                  7
                  5
                  3
        2    9    1
             7
             5
             3
             1
        1

       0.5


       0.3        9
                  7
                  5
                  3
       0.2        1
                                             13 57 9         15 9              13 57 9
                                                                                     13 57 9  15 9
                                    1  3  5  7  9                    1  3  5  7  9
       0.1
           2     3      5         10        20    30     50        100       200   300    500        1000
                                               26.5                                              Breaking current Ic (A)

       Example:
       Ic / AC-1 = 26.5 A – Electrical durability required = 2 millions operating cycles.
       Using the AC-1 curves above select the AF26 contactor at intersection " " (26.5 A / 2 millions operating cycles).




















                                                                                                                  1SBC101940S0201






       5/150  |  ABB
   345   346   347   348   349   350   351   352   353   354   355