Page 351 - Motor_protection_and_control_Manual_motor_starters_ contactors
P. 351

3-pole contactors

         Electrical durability





         Electrical durability for AC-3 utilization category - Ue ≤ 440 V.
         Switching cage motors: starting and switching off running motors. The breaking current Ic for AC-3 is equal to the rated opera-
         tional current Ie (Ie = motor full load current).
         Ambient temperature and maximum electrical switching frequency: see "Technical data".


         Millions of                                                                               AF1350, AF1650:
                                                                                                   The electrical durability at
         operating              AF30, AF38      AF80, AF96   AF140, AF146                          the rated current is 50000
         cycles  AF09  AF12  AF16  AF26  AF40  AF52  AF65  AF116  AF190  AF205 AF265 AF305 AF370  AF400 AF460  AF580  AF750  operating cycles.
          10


           5

                                                                                                                    5
           3        9
                    7
                    5
                    3
           2    9   1
         1.8    7
                5
                3
           1    1


          0.5

              13 57 9                         13 57 9     15 9                13 57 9
          0.3
                                                                                   13 57 9
                                     1  3  5  7  9     15 9          1  3  5  7  9
          0.2
             2     3      5        10        20   30     50        100      200   300    500       1000
                                                           55                                      Breaking current Ic (A)
         Example:
         Motor power 30 kW for AC-3 - Ue = 400 V and Ie = 55 A utilization – Electrical durability required = 1.8 million operating cycles.
         For AC-3: Ic = Ie. Select the AF65 contactor at intersection " " (55 A / 1.8 million operating cycles) on the curves (AC-3 - Ue ≤ 440 V).




























                                                                                                                    1SBC101941S0201






                                                                                                         ABB  |  5/151
   346   347   348   349   350   351   352   353   354   355   356