AF116 ... AF370  4-pole contactors

         Technical data





         Main pole - Utilization characteristics according to IEC
         Contactor types             AC / DC operated AF116  AF140  AF190  AF205  AF265  AF305  AF370  EK550  EK1000
         Standards                               IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
         Rated operational voltage Ue max.       690 V        1000 V
         Rated frequency (without derating)      50 / 60 Hz
         Conventional free-air thermal current Ith
         acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C  160 A  200 A  275 A  350 A  400 A  500 A  525 A  800 A  1000 A
           With conductor cross-sectional area   70 mm²  95 mm²  150  mm² 240 mm²  240 mm² 300 mm²  2x    2x    2x
                                                                     (3)           (4)    185 mm² (4)  240 mm²  300 mm²
         AC-1 Utilization category
         For air temperature close to contactor
           Ie / Rated operational current AC-1  θ ≤ 40 °C 160 A  200 A  275 A  350 A  400 A  500 A  525 A  800 A  1000 A
           Ue max. ≤ 690 V, 50/60 Hz      θ ≤ 60 °C 145 A  175 A  250 A  300 A  350 A  400 A  425 A  650 A  800 A
                                          θ ≤ 70 °C 130 A  160 A  200 A  240 A  290 A  325 A  350 A  575 A  720 A
           Ue max. ≤ 1000 V, 50/60 Hz     θ ≤ 40 °C -  -      250 A  275 A  350 A  375 A  400 A    800 A    1000 A
                                        θ ≤ 60 °C (2) -  -    225 A  250 A  300 A  325 A  350 A    650 A    800 A
                                          θ ≤ 70 °C -  -      185 A  200 A  240 A  260 A  290 A    575 A    720 A
           With conductor cross-sectional area   70 mm²  95 mm²  150 mm²  240 mm²  240 mm² 300 mm²  2x 185 mm²  2x    2x    5
                                                                     (3)           (4)    (4)      240 mm²  300 mm²
         AC-3 Utilization category
         For air temperature close to contactor θ ≤ 60 °C (2)
           Ie / Max. rated operational current AC-3 (1)
                                       220-230-240 V 116 A  140 A  190 A  205 A  265 A  305 A  370 A  550 A  -
                                         380-400 V 116 A  140 A  190 A  205 A  265 A  305 A  370 A  550 A   -
                                            415 V 116 A  140 A  190 A  205 A  265 A  305 A  370 A  550 A    -
              M     3-phase motors          440 V 116 A  140 A  190 A  205 A  265 A  305 A  370 A  550 A    -
             3                              500 V -    -      -      -      -      -      -        550 A    -
                                            690 V -    -      -      -      -      -      -        550 A    -
                                           1000 V -    -      -      -      -      -      -        175 A    -
           Rated operational power AC-3 (1)
                                       220-230-240 V 30 kW  37 kW  55 kW  55 kW  75 kW  90 kW  110 kW  160 kW  -
                                         380-400 V 55 kW  75 kW  90 kW  110 kW  132 kW  160 kW  200 kW  280 kW  -
                                            415 V 55 kW  75 kW  90 kW  110 kW  132 kW  160 kW  200 kW  315 kW  -
                    1500 r.p.m. 50 Hz
              M     1800 r.p.m. 60 Hz       440 V 75 kW  90 kW  110 kW  132 kW  160 kW  160 kW  200 kW  315 kW  -
             3      3-phase motors          500 V -    -      -      -      -      -      -        400 kW   -
                                            690 V -    -      -      -      -      -      -        500 kW   -
                                           1000 V -    -      -      -      -      -      -        250 kW   -
         Rated making capacity AC-3              10 x Ie AC-3 acc. to IEC 60947-4-1
         Rated breaking capacity AC-3            8 x Ie AC-3 acc. to IEC 60947-4-1
         Short-circuit protection device for contactors
         Without thermal overload relay - Motor protection excluded
         Ue ≤ 500 V AC - gG type fuse            200 A  250 A  355 A  400 A  630 A  630 A  630 A   800 A    1000 A
         Rated short-time withstand current Icw  1 s 1300 A  1460 A  1900 A  2050 A  2650 A  3050 A  3700 A  5500 A  6800 A
         At 40 °C ambient temperature,       10 s 928 A  1168 A  1520 A  1640 A  2120 A  2440 A  2960 A  5300 A  6400 A
         in free air from a cold state       30 s 536 A  674 A  878 A  947 A  1224 A  1409 A  1709 A  3700 A  4400 A
                                            1 min 379 A  477 A  621 A  670 A  865 A  996 A  1208 A  3000 A  3400 A
                                           15 min 160 A  200 A  275 A  350 A  400 A  500 A  525 A  1000 A   1200 A
         Maximum breaking capacity        at 440 V 2000 A  3000 A  3300 A  3500 A  3800 A  4600 A  5000 A  5400 A  -
         cos φ = 0.45                     at 690 V -   -      -      -      -      -      -        5400 A   -
         Power dissipation per pole       Ie / AC-1 12 W  18 W  15 W  25 W  32 W   50 W   72 W     60 W     80 W
                                          Ie / AC-3 -  -      -      -      -      -      -        25 W     -
         Max. electrical switching frequency  AC-1 300 cycles/h
                                            AC-3 300 cycles/h                                               -
                                         AC-2, AC4 -                                               120 cycles/h -
         (1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
         (2) θ ≤ 55 °C for EK550, EK1000
         (3) For currents above 275 A use terminal enlargements or terminal extensions.
         (4) For currents above 450 A use terminal enlargements or terminal extensions.







                                                                                                                    1SFC101209C0201 - Rev. B