Page 737 - Motor_protection_and_control_Manual_motor_starters_ contactors
P. 737
TF140DU thermal overload relays – 66 to 142 A
Technical data
Main circuit – Utilization characteristics according to UL/CSA
Type TF140DU / TF140DU-V1000
Standards UL 508, CSA 22.2 No. 14, UL 60947-4-1A
Maximum operational voltage 600 V AC
Trip rating 125% of FLA
Full load amps (FLA) See table "Full load amps and short-circuit protective device"
Short-circuit rating RMS symmetrical See table "Full load amps and short-circuit protective device"
Short-circuit protective device See table "Full load amps and short-circuit protective device"
Auxiliary circuit according to UL/CSA
Type TF140DU / TF140DU-V1000
Contact rating N.C., 95-96 B600
N.O., 97-98 C300
Conventional thermal current N.C./N.O. 10 A / 6 A
Full load amps and short-circuit protective device
Type Full load amps (FLA) Short-circuit protective device
480 / 600 V AC 480 / 600 V AC 480 / 600 V AC
Short circuit rating Fuse type Short circuit rating Fuse type Short circuit rating Listed circuit breaker
RMS symmetrical RMS symmetrical RMS symmetrical
TF140DU-90 / 90 A 10 kA 250 A, K5 / RK5 100 kA 250 A, Class J 100 kA 250 A 7
TF140DU-90-V1000
TF140DU-110 / 110 A 10 kA 250 A, K5 / RK5 100 kA 250 A, Class J 100 kA 250 A
TF140DU-110-V1000
TF140DU-135 / 135 A 10 kA 250 A, K5 / RK5 100 kA 250 A, Class J 100 kA 250 A
TF140DU-135-V1000
TF140DU-142 / 142 A 10 kA 250 A, K5 / RK5 100 kA 250 A, Class J 100 kA 250 A
TF140DU-142-V1000
2CDC106054C0201
ABB | 7/23