AF50..RT ... AF95B..RT  3-pole contactors

         Technical data





         Main pole - Utilization characteristics according to IEC
         Contactor types                           AF50..RT        AF63..RT        AF75..RT        AF95B..RT
         Standards                                 IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
                                                   IEC 60077-1, IEC 60077-2, EN 50155 (applicable parts)  (3)
         Fire and smoke                            EN 45545-2 (HL2, HL3)                           EN 45545-2 (HL2)
         Rated operational voltage Ue max.         690 V                                           1000 V
         Rated frequency (without derating)        50/60 Hz
         Conventional free-air thermal current Ith
         acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C  100 A  115 A           125 A           145 A            3
           With conductor cross-sectional area     2 x 25 mm²      2 x 25 mm²      2 x 25 mm²      50 mm²
         AC-1 Utilization category
         For air temperature close to contactor
           Ie / Rated operational current AC-1  θ ≤ 40 °C 100 A    115 A           125 A           145 A
           Ue max. ≤ 690 V, 50/60 Hz        θ ≤ 55 °C 85 A         95 A            105 A           135 A
                                            θ ≤ 70 °C 70 A         80 A            85 A            115 A
           With conductor cross-sectional area     2 x 25 mm²      2 x 25 mm²      2 x 25 mm²      50 mm²
           Ie / Rated operational current AC-1  θ ≤ 40 °C 80 A     90 A            95 A            -
           Ue max. ≤ 690 V, 50/60 Hz        θ ≤ 55 °C 68 A         75 A            80 A            -
                                            θ ≤ 70 °C 55 A         60 A            65 A            -
           With conductor cross-sectional area     1 x 25 mm²      1 x 25 mm²      1 x 25 mm²      -
         AC-3 Utilization category
         For air temperature close to contactor θ ≤ 55 °C
           Ie / Max. rated operational current AC-3 (1)
                                        220-230-240 V 53 A         65 A            75 A            96 A
                                           380-400 V 50 A          65 A            75 A            96 A
                                              415 V 50 A           65 A            75 A            96 A
             M      3-phase motors            440 V 45 A           65 A            70 A            93 A
             3                                500 V 45 A           55 A            65 A            80 A
                                              690 V 35 A           43 A            46 A            65 A
                                             1000 V -              -               -               30 A
           Rated operational power AC-3 (1)
                                        220-230-240 V 15 kW        18.5 kW         22 kW           25 kW
                                           380-400 V 22 kW         30 kW           37 kW           45 kW
                                              415 V 25 kW          37 kW           40 kW           55 kW
                    1500 r.p.m. 50 Hz
             M      1800 r.p.m. 60 Hz         440 V 25 kW          37 kW           40 kW           55 kW
             3      3-phase motors            500 V 30 kW          37 kW           45 kW           55 kW
                                              690 V 30 kW          37 kW           40 kW           55 kW
                                             1000 V -              -               -               40 kW
         Rated making capacity AC-3                10 x Ie AC-3 acc. to IEC 60947-4-1
         Rated breaking capacity AC-3              8 x Ie AC-3 acc. to IEC 60947-4-1
         Short-circuit protection device for contactors
         without thermal overload relay - Motor protection excluded (2)
         Ue ≤ 500 V AC - gG type fuse              100 A           125 A           160 A           160 A
         Rated short-time withstand current Icw  1 s 1000 A                                        1320 A
         at 40 °C ambient temperature,         10 s 650 A                                          800 A
         in free air from a cold state         30 s 370 A                                          500 A
                                              1 min 250 A                                          350 A
                                             15 min 110 A          135 A           135 A           160 A
         Maximum breaking capacity
         cos φ = 0.45                       at 440 V 1300 A                                        1160 A
         (cos φ = 0.35 for Ie > 100 A)      at 690 V 630 A                                         800 A
         Power dissipation per pole         Ie / AC-1 5 W          6.5 W           7 W             6.5 W
                                            Ie / AC-3 1.3 W        1.5 W           2 W             2.7 W
         Max. electrical switching frequency  AC-1 300 cycles/h
                                              AC-3 300 cycles/h
                                              AC-4 150 cycles/h
         (1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
                                                                                                                    1SBC100075S0201 - Rev.A
         (2) For the protection of motor starters against short circuits, see "Coordination with short-circuit protection devices".
         (3) AF95B: please consult us.