Climatic withstand of devices

General
The life time and dependability of devices are mainly influenced by a series of climatic factors which cause their corrosion.
In practice, besides climatic conditions, there are other factors which may damage equipment such as fungi, insects (termites), dust, work site dirt
and aggressive environment (salty or sulphurous atmosphere, etc.) which can often only be identified at the place of installation.
The entrance of dust, insects, dirt, etc. in devices may be prevented if the appropriate degree of protection according to IEC 60529 is chosen.
ABB contactors have been used for many years in the most varied countries, with hot and humid climates for example: Brazil, Indonesia, India etc.
Experience has shown that ABB devices can be used in most countries throughout the world.
The climate of the country in which the device is installed is not the determining choice factor.

Account must be taken of:
–– the immediate environment of the devices (sheltered, ventilated, temperature)
–– the aggressivity of the immediate atmosphere at the place of installation
–– the length and frequency of non operating periods.

In the case of frequent condensation (Ie the formation of steam caused by rapid changes in temperature), heating resistors must be installed in
cubicles (100 to 250 W per m3 of enclosure).

The table below gives the cases where heating is necessary.

Environment              no running water,            Operating conditions        Climate           Internal heating of enclosure
Inside premises          no condensation              Continuous or not           All climates      Without

                         with running water           Continuous                  All climates      Without
                                                      Frequent or long stops      Temperate         Without
                                                                                  Tropical          With
Outside, sheltered       no running water,            Continuous or not           Temperate         Without
                         no condensation
                                                                                  Tropical          With
        Outside or by the seaside with running water  Continuous                  All climates      Without
                                                      Frequent or long stops      Temperate         Without
10                                                                                Tropical          With

The standard R series contactors are suitable for industrial environment and tropical atmospheres.