Page 48 - 1SBC104119C0202_MainCatalog_R contactors
P. 48
IORR63..CC … IORR500..CC and
IORE63..CC … IORE500..CC contactors
Technical data
Main pole - Utilization characteristics according to IEC
Contactor types AC operated IORR63..CC IORR125..CC IORR200..CC IORR400..CC IORR500..CC
IORE400..CC IORE500..CC
DC operated IORE63..CC IORE125..CC IORE200..CC
400 A 550 A
Standards IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1 240 mm² 400 mm²
Rated operational voltage Ue max. 1000 V DC (1500 V DC with increased insulation (1)) 400 A 550 A
400 A 550 A
Number of poles 1...4 400 A 550 A
Conventional free-air thermal current Ith
acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C 85 A 170 A 275 A
With conductor cross-sectional area 25 mm² 70 mm² 150 mm²
DC-1 Utilization category, L/R ≤ 1 ms
Ie / Rated operational current DC-1
1 pole ≤ 500 V 85 A 170 A 275 A
4
2 poles in series
≤ 1000 V 85 A 170 A 275 A
≤ 1500 V (1) - - -
3 poles in series
≤ 1500 V (1) 85 A 170 A 275 A 400 A 550 A
DC-3 Utilization category, L/R ≤ 2 ms
Ie / Rated operational current DC-3
1 pole
≤ 500 V 68 A 125 A 205 A 350 A 500 A
2 poles in series
≤ 1000 V 68 A 125 A 205 A 350 A 500 A
3 poles in series
≤ 1500 V (1) 68 A 125 A 205 A 350 A 500 A
DC-5 Utilization category, L/R ≤ 7.5 ms
Ie / Rated operational current DC-5
1 pole
≤ 500 V 68 A 125 A 205 A 350 A 500 A
2 poles in series
≤ 1000 V 68 A 125 A 205 A 350 A 500 A
3 poles in series
Rated short-time withstand current Icw ≤ 1500 V (1) 68 A 125 A 205 A 350 A 500 A
at 40 °C ambient temperature, 1s 1150 A 2250 A 3800 A 6000 A 8400 A
in free air from a cold state 680 A 1280 A 2080 A 3200 A 4400 A
10 s 310 A 680 A 1040 A 1600 A 2200 A
Rated breaking capacity 30 s 230 A 450 A 730 A 1200 A 1680 A
(L/R ≤ 15 ms) 1 min 120 A 250 A 390 A 600 A 840 A
15 min
Maximum making capacity 500 A 820 A 1400 A 2000 A
Dynamical withstand of pole 1 pole 500 V 272 A 500 A 820 A 1400 A 2000 A
Impedance per pole 2 poles 1000 V 272 A 500 A 820 A 1400 A 2000 A
Maximum electrical switching frequency 3 poles 1500 V 272 A 2400 A 4000 A 7000 A 9000 A
Mechanical durability 1300 A 2500 A 4500 A 8000 A 10000 A
1400 A 1.20 mΩ 0.60 mΩ 0.40 mΩ 0.35 mΩ
Number of operating cycles 1.8 mΩ
Maximum switching frequency 120 cycles/h
5 millions cycles
1200 cycles/h
(1) Version with increased insulation for 1000 V < Ue < 1500 V, please consult us. 1SBC104034S0201
Notes: - The arc switching on DC is more difficult than on AC
- For information, typical time constant values are quoted hereafter: non inductive loads such as resistance furnaces: L/R < 1 ms; inductive loads such as shunt motor:
L/R < 2 ms; series motor: L/R < 7.5 ms
- The addition of a resistor in parallel with an inductive winding helps in the elimination of the arcs
- All the poles required for breaking must be connected, in series, between the load and the source polarity not linked to the earth
- Connection of the poles in series by the user, according to the above diagrams. The connection of the poles in series helps in the elimination of the arcs
- These characteristics are suitable for IOR..CC-AMA and IOR..CC-AME contactor latching versions (except for mechanical durability = 0.2 millions of operating cycles).
4/10 | ABB R contactors