Page 49 - 1SBC104119C0202_MainCatalog_R contactors
P. 49
IORR800..CC … IORR2100..CC and
IORE800..CC … IORE2100..CC contactors
Technical data
Main pole - Utilization characteristics according to IEC
Contactor types AC operated IORR800..CC IORR1000..CC IORR1400..CC IORR1700..CC IORR2100..CC
IORE1700..CC IORE2100..CC
Standards DC operated IORE800..CC IORE1000..CC IORE1400..CC
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1 1700 A 2000 A
1500 mm² 1500 mm²
Rated operational voltage Ue max. 1500 V DC
Number of poles 1...4
Conventional free-air thermal current Ith
acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C 800 A 1000 A 1300 A
With conductor cross-sectional area 500 mm² 600 mm² 1000 mm²
DC-1 Utilization category, L/R ≤ 1 ms
Ie / Rated operational current DC-1
1 pole 4
2 poles in series ≤ 750 V 800 A 1000 A 1250 A 1600 A 2000 A
DC-3 Utilization category, L/R ≤ 2 ms ≤ 1000 V 800 A 1000 A 1250 A 1600 A 2000 A
Ie / Rated operational current DC-3 ≤ 1500 V 800 A 1000 A 1250 A 1600 A 2000 A
1 pole
≤ 600 V 720 A 1000 A 1250 A 1600 A 2000 A
2 poles in series
≤ 1000 V 720 A 1000 A 1250 A 1600 A 2000 A
3 poles in series
≤ 1500 V 720 A 1000 A 1250 A 1600 A 2000 A
DC-5 Utilization category, L/R ≤ 7.5 ms
Ie / Rated operational current DC-5
1 pole
≤ 600 V 720 A 1000 A 1250 A 1600 A 2000 A
2 poles in series
≤ 1000 V 720 A 1000 A 1250 A 1600 A 2000 A
3 poles in series
Rated short-time withstand current Icw ≤ 1500 V 720 A 1000 A 1250 A 1600 A 2000 A
at 40 °C ambient temperature, 1s 9000 A 9000 A 11000 A 13000 A 15000 A
in free air from a cold state 6400 A 6400 A 9000 A 11000 A 12000 A
10 s 3200 A 3200 A 5000 A 6000 A 7000 A
Rated breaking capacity 30 s 2100 A 2100 A 3600 A 4200 A 4600 A
(L/R ≤ 15 ms) 1 min 1200 A 1200 A 1900 A 2200 A 2600 A
15 min
Maximum making capacity 4000 A 5000 A 6400 A 8000 A
Dynamical withstand of pole 1 pole 600 V 2880 A 4000 A 5000 A 6400 A 8000 A
Impedance per pole 2 poles 1000 V 2880 A 4000 A 5000 A 6400 A 8000 A
Maximum electrical switching frequency 3 poles 1500 V 2880 A 14000 A 19000 A 21000 A 24000 A
Mechanical durability 14000 A 14000 A 19000 A 21000 A 24000 A
14000 A 0.24 mΩ 0.18 mΩ 0.12 mΩ 0.10 mΩ
Number of operating cycles 0.28 mΩ 60 cycles/h
Maximum switching frequency 120 cycles/h
2 millions cycles
5 millions cycles 600 cycles/h
1200 cycles/h
Notes: - The arc switching on DC is more difficult than on AC
- For information, typical time constant values are quoted hereafter: non inductive loads such as resistance furnaces: L/R < 1 ms; inductive loads such as shunt motor:
L/R < 2 ms; series motor: L/R < 7.5 ms
- The addition of a resistor in parallel with an inductive winding helps in the elimination of the arcs
- All the poles required for breaking must be connected, in series, between the load and the source polarity not linked to the earth
- Connection of the poles in series by the user, according to the above diagrams. The connection of the poles in series helps in the elimination of the arcs
- These characteristics are suitable for IOR..CC-AME contactor latching versions (except for mechanical durability = 0.2 millions of operating cycles).
1SBC104035S0201
ABB R contactors | 4/11