Page 33 - Kabeldon
P. 33

Switching devices with independent manual operation

         LBOD, SLOC, 540 A–1250 A












                                                                                                                    2

















         LBOD 800                         LBOD 1000                          LBOD 1600
         Section switch disconnector without fuse    Section switch disconnector without fuse    Section switch disconnector without fuse
         up to 785 A. To be mounted on Kabeldon    up to 1000 A. To be mounted on Kabeldon    up to 1250 A. To be mounted on Kabeldon
         IP-system. Degree of protection IP2X.  IP-system. Degree of protection IP2X.  IP-system. Degree of protection IP2X.


















         SLOC 630                                                            LBOD 1600 with divided busbar supports in
         Section switch-fuse with breaking on both                           both sides.
         sides of the fuse. 3-pole breaking with
         sealing possibility. System always dead
         when replacing fuses. Degree of protection
         IP2X.
         Note:
            − Switching devices to be tightened with torque. For
           “Tightening torque” see page 5/6.






          Designation  ID-number  Number of modules  Rated current [A]  Fits in enclosure type Weight
                               M*            Enclosure Open air             kg/pcs
          LBOD 800  2CGX0 63050252  27       680     785     KSIK, SDC      11,1
         LBOD 1000  2CGX0 63050253  27       950     1000    KSIK, SDC      16,6
         LBOD 1600  2CGX0 63050254  38       1250    1325    KSIK, SDC      19,8
         SLOC 630  2CGX0 63050250  27        540     615     KSIK, SDC      14,5
         * 1 module M = 12,5 mm.





                                                             | Switching devices | Kabeldon fusegear and cable distribution cabinets | 2016 |  2/16