Page 35 - Kabeldon
P. 35
Connectors
Installation of Kabeldon AD 300
2
ADC 25 AD 70 ADO 240 AD 350
Non-insulated connector. Non-insulated connector. Non-insulated connector. Non-insulated connector for connect-
May only be used with May only be used with May only be used with non- ing three separate conductors.
non-protected busbars. non-protected busbars. protected busbars. May only be used with non-protected
busbars.
AD 95 AD 2150 AD 300 AD 400
Insulated connector. Insulated connector Insulated connector. Insulated connector.
for parallel conductors.
KSBH 300
Cover for disconnected cable, for
protection against accidental contact,
with AD 300 or AD 2150.
ADB 3M STM 400 ADP 300 ADN
Insulated connector Conductor rail with connector Insulated connector for parallel Spacer for PEN bar, used with AD 300.
for compact fitting of for current transformer conductors with fuse-switch-
AD 300 for 3 phases. metering. Dimensions of disconnectors SLD 1, SLD 2
conductor rail are 25x13 mm. and also circuit-breakers
Note: ABB Tmax T5.
Switching devices and connectors must be tightened to the
recommended torque. For “Tightening torque” see page 5/6.
Designation ID No. Number of modules Width Rated data Degree of Cable connection Al/Cu ** Weight
M * mm V A protection mm² kg/pcs
ADC 25 2CGX0 63030233 – 14 – 63 – 2 x 1,5-25 0,1
AD 70 2CGX0 63030038 – 23 – 200 – 6-95 0,1
ADO 240 2CGX0 63030263 3 30 – 400 – 120-240 0,25
AD 350 2CGX0 63030262 – 38 – 400 – 3 x 6-50 0,2
AD 95 2CGX0 63030249 2 25 690 200 IP2X 6-95 0,1
AD 2150 2CGX0 63030037 3 38 690 400 IP2X 35-2//150 0,2
AD 300 *** 2CGX0 63030195 3 38 690 630 IP2X 50-300 0,2
AD 400 2CGX0 63030267 3 42 690 630 IP2x 50-400 0,47
ADB 3M **** 2CGX0 63030258 3 38 500 500 IP2X – 0,7
STM 400 2CGX0 63090026 3 35 400 400 IP2X 50-300 0,4
ADP 300 2CGX0 63090035 3 38 690 630 IP2X 2//50-300 0,8
KSBH 300 2CGX0 63190111 – 46 – – – – 0,1
ADN 2CGX0 63030231 – 37 – 500 – – 0,3
* One module M = 12.5 mm.
** Max conductor cross section refers to connection with a stranded or solid conductor.
*** Three-phase connection, 6-9 modules.
**** ADB 3M to be supplemented with three AD 300
| Switching devices | Kabeldon fusegear and cable distribution cabinets | 2016 | 2/18