Page 35 - Kabeldon
P. 35

Connectors







                                                               Installation of Kabeldon AD 300






                                                                                                                    2



         ADC 25                     AD 70                      ADO 240                    AD 350
         Non-insulated connector.   Non-insulated connector.   Non-insulated connector.    Non-insulated connector for connect-
         May only be used with      May only be used with      May only be used with non-  ing three separate conductors.
         non-protected busbars.     non-protected busbars.     protected busbars.         May only be used with non-protected
                                                                                          busbars.








         AD 95                      AD 2150                    AD 300                     AD 400
         Insulated connector.       Insulated connector        Insulated connector.       Insulated connector.
                                    for parallel conductors.




                                                                                          KSBH 300
                                                                                          Cover for disconnected cable, for
                                                                                          protection against accidental contact,
                                                                                          with AD 300 or AD 2150.



         ADB 3M                     STM 400                    ADP 300                    ADN
         Insulated connector        Conductor rail with connector   Insulated connector for parallel    Spacer for PEN bar, used with AD 300.
         for compact fitting of     for current transformer    conductors with fuse-switch-
         AD 300 for 3 phases.       metering. Dimensions of    disconnectors SLD 1, SLD 2
                                    conductor rail are 25x13 mm.  and also circuit-breakers
         Note:                                                 ABB Tmax T5.
         Switching devices and connectors must be tightened to the
         recommended torque. For “Tightening torque” see page 5/6.

          Designation  ID No.      Number of modules  Width  Rated data  Degree of    Cable connection Al/Cu **  Weight
                                        M *        mm     V      A    protection        mm²           kg/pcs
          ADC 25    2CGX0 63030233       –          14    –      63      –            2 x 1,5-25       0,1
          AD 70     2CGX0 63030038       –          23    –     200      –              6-95           0,1
          ADO 240   2CGX0 63030263       3          30    –     400      –            120-240          0,25
          AD 350    2CGX0 63030262       –          38    –     400      –             3 x 6-50        0,2
          AD 95     2CGX0 63030249       2          25    690   200     IP2X            6-95           0,1
          AD 2150   2CGX0 63030037       3          38    690   400     IP2X          35-2//150        0,2
          AD 300 ***  2CGX0 63030195     3          38    690   630     IP2X           50-300          0,2
          AD 400    2CGX0 63030267       3          42    690   630     IP2x           50-400          0,47
          ADB 3M ****  2CGX0 63030258    3          38    500   500     IP2X             –             0,7
          STM 400   2CGX0 63090026       3          35    400   400     IP2X           50-300          0,4
          ADP 300   2CGX0 63090035       3          38    690   630     IP2X          2//50-300        0,8
          KSBH 300  2CGX0 63190111       –          46    –      –       –               –             0,1
          ADN       2CGX0 63030231       –          37    –     500      –               –             0,3
         * One module M = 12.5 mm.
         ** Max conductor cross section refers to connection with a stranded or solid conductor.
         *** Three-phase connection, 6-9 modules.
         **** ADB 3M to be supplemented with three AD 300
                                                             | Switching devices | Kabeldon fusegear and cable distribution cabinets | 2016 |  2/18
   30   31   32   33   34   35   36   37   38   39   40