Page 593 - Motor_protection_and_control_Manual_motor_starters_ contactors
P. 593

Mechanical and electrical interlock units








         Technical data
         Types                                      VE5-2
         Contact utilization characteristics according to IEC
         Standards                                  IEC 60947-5-1 and EN 60947-5-1
         Rated insulation voltage Ui acc. to IEC 60947-5-1  690 V
         Rated operational voltage Ue max.          24...690 V
         Conventional thermal current Ith - θ ≤ 40 °C  16 A
         Ie / Rated operational current AC-15
         acc. to IEC 60947-5-1          24-127 V 50/60 Hz 6 A
                                       220-240 V 50/60 Hz 4 A
                                       380-440 V 50/60 Hz 3 A
                                       500-690 V 50/60 Hz 2 A
         Making capacity acc. to IEC 60947-5-1      10 x Ie AC-15
         Breaking capacity acc. to IEC 60947-5-1    10 x Ie AC-15
         Ie / Rated operational current DC-13
         acc. to IEC 60947-5-1                24 V DC 6 A                                                           5
                                              48 V DC 2.8 A
                                              72 V DC 1 A
                                             125 V DC 0.55 A
                                             250 V DC 0.3 A
         Short-circuit protection device - gG type fuse  10 A
         Rated short-time withstand current Icw  for 1.0 s 100 A
         θ = 40 °C                            for 0.1 s 140 A
         Power dissipation per pole at 6 A          0.15 W
         Mechanical durability
           Number of operating cycles               5 millions operating cycles
         Max. switching frequency                   600 cycles/h
         Utilization characteristics according to UL/CSA
         Standards                                  UL 508, CSA C22.2 N°14
         Max. operational voltage                   600 V
         Connecting characteristics
         Connection capacity (min. ... max.)
                   Rigid solid                   1 x 1...4 mm²
                                                 2 x 1...4 mm²
                   Flexible with ferrule         1 x 0.75...2.5 mm²
                                                 2 x 0.75...2.5 mm²
                   Lugs                          L < 8 mm
                 l  L
                                                 l > 3.5 mm
         Tightening torque
           Recommended                              1 Nm
           Max.                                     1.2 Nm
         Degree of protection                       IP20
         acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
         Screw terminals                            delivered in open position, screws of unused terminals must be tightened
           All terminals                            M3.5
         Screwdriver type                           Flat Ø 5.5 / Pozidriv 2
         Terminal marking                             01       01
                                                      NC       NC
                                                      02       02  E0085D1
         Technical note: when, during switching, the arc time is estimated to more than 40 ms, the closing signal of one of the two contactors must be delayed with respect to the opening
         signal of the other contactor in order to prevent a short-circuit.
         Use a TEF5 electronic timer according to application use with time lapse for GA75, GAE75 contators.





                                                                                                                    1SBC101331S0201 - Rev. B