Page 589 - Motor_protection_and_control_Manual_motor_starters_ contactors
P. 589

Electronic timers

         Technical data





         Contact utilization characteristics according to IEC
         Types                                   TEF5-ON                          TEF5-OFF
         Standards                               IEC 60947-5-1 and EN 60947-5-1
         Rated insulation voltage Ui
         acc. to IEC 60947-5-1                   400 V
         Rated impulse withstand voltage Uimp    4 kV
         Rated operational voltage Ue max.       240 V
         Rated frequency (without derating)      50 / 60 Hz
         Conventional thermal current Ith - θ ≤ 40 °C  5 A                                                          3
         Ie / Rated operational current AC-15
         acc. to IEC 60947-5-1       24-127 V 50/60 Hz 3 A
                                    220-240 V 50/60 Hz 1.5 A
         Making capacity                         10 x Ie AC-15 acc. to IEC 60947-5-1
         Breaking capacity                       10 x Ie AC-15 acc. to IEC 60947-5-1
         Ie / Rated operational current DC-13
         acc. to IEC 60947-5-1            24 V DC 1 A / 24 W
         Short-circuit protection device gG type fuse  6 A
         Rated short-time withstand current Icw  for 1.0 s 8 A
         θ = 40 °C                        for 0.1 s 8 A
         Minimum switching capacity              12 V / 3 mA
         with failure rate acc. to IEC 60947-5-4  24 V DC 10 -7
         Power dissipation per pole at 3 A       0.1 W
         Function diagram                        ON-delay                         OFF-delay
                                                                        150 ms                1 s
                                                                         min.                 min.
                                                  Uc (A1 - A2)                     Uc (A1 - A2)
                                                                     100 ms                              100 ms
                                                                     min.                                 min.
                                                  N.O. (67 - 68)                   N.O. (67 - 68)
                                                  N.C. (55 - 56)                   N.C. (55 - 56)
                                                                t                                    t
                                                 Bistable relay inside.
                                                 Before use, once apply Uc then switch it off in order to initialize position of the contacts.
         Control circuit voltage
           AC control voltage  Rated control circuit voltage Uc  24...240 V AC
           50/60 Hz       Average consumption    1.5 mA RMS                       1 mA RMS
           DC control voltage  Rated control circuit voltage Uc  24...240 V DC
                          Average consumption    1.5 mA                           1 mA
           Rated frequency limits                50 / 60 Hz
           Supply voltage range                  0.85...1.1 x Uc (at θ ≤ 70 °C)
           Overvoltage protection                Varistor included
         Time delay range (t) selected by switch  0.1...1 s
                                           1...10 s
                                          10...100 s
           On-load reiteration accuracy under constant conditions  ≤ 1 %
           Minimum ON period                     0.1 s                            1 s
           Recovery time                         0.15 s                           0.1 s
         Ambient air temperature  Operation      -25 °C ... +70 °C
                          Storage                -40 °C ... +80 °C
         Climatic withstand                      Category B according to IEC 60947-1 Annex Q
         Maximum operating altitude              2000 m
         Mounting positions                      Acc. to mounting positions permitted on contactors or contactor relays
         Shock withstand                         1/2 sinusoidal shock for 11 ms: no change in contact position
         acc. to IEC 60068-2-27 and EN 60068-2-27  Same as contactor or contactor relay
         (Mounting position 1)
         Mechanical durability
                          Number of operating cycles  5 millions operating cycles
                          Max. switching frequency  3600 cycles/h                 1800 cycles/h
         Max. electrical switching frequency
                                            AC-15 1200 cycles/h
                                           DC-13 900 cycles/h
                                                                                                                    1SBC101674S0201 - Rev. A








                                                                                                           ABB  |  389
   584   585   586   587   588   589   590   591   592   593   594