Auxiliary contacts for AF45 ... AF95B contactors
       Electrical durability






       Electrical durability for AC-15 utilization category
       AC-15 utilization category according to IEC 60947-5-1 / EN 60947-5-1:
          – making current: 10 x Ie with cos ϕ = 0.7 and Ue
          – breaking current: Ie with cos ϕ = 0.4 and Ue.
       These curves represent the electrical durability of the built-in or add-on auxiliary contacts, in relation to the breaking current.
       The curves have been drawn for resistive and inductive loads up to 690 V, 40...60 Hz.
    3
           30                                                   – 1-pole and 4-pole CA5,
           20
                                                               1-pole CC5,
           10
                                                               2-pole CAL5 and CAL18 add-on auxiliary contacts.
           5 3 2                                             Example:
        Million operating cycles  0.5 1                      Breaking current = 1.2 A
         2.7
                                                             On the opposite curve at intersection "O" 1.2 A
                                                             the corresponding value for the electrical durability is
          0.3
          0.2
                                                                              6
          0.1                                                approximately 2.7.10  operating cycles.
            0.02  0.05  0.1  0.2  0.3  0.5  1 1.2  2  3  45 6  10
                                Breaking current (A)






       Electrical durability for DC-13 utilization category
       DC-13 utilization category according to IEC 60947-5-1 / EN 60947-5-1: making and breaking current = Ie with Ue value.

                                                                – 1-pole and 4-pole CA5,
          100                                                  1-pole CC5,
          70                                  1.10  cycles     2-pole CAL5 and CAL18 add-on auxiliary contacts.
                                                6
           50
                                                6
                                              3.10  cycles   Example:
        Breaking power (W)  10 5             10.10  cycles   Control of DC electro-magnet: Ue voltage = 72 V DC and
           20
                                                6
                                                             breaking power = 70 W.
                                                             On the opposite curve at intersection "O" 72 V / 70 W
                                                              the corresponding value for the electrical durability is
           2
                                                             approximately 2.10  operating cycles.
                                                                             6
           1
            10     20 24    50  72  100  200  250  500
                                      Voltage (V)