Page 640 - Motor_protection_and_control_Manual_motor_starters_ contactors
P. 640
AS09..S ... AS16..S and
ASL09..S ... ASL16..S 3-pole contactors - with spring terminals
Electrical durability
Electrical durability for AC-1 utilization category - Ue ≤ 690 V
Note: AC-1 maximum current is selected according to ambient temperature. Please see technical data.
Switching non-inductive or slightly inductive loads. The breaking current Ic for AC-1 is equal to the rated operational current of
the load. Maximum electrical switching frequency: 600 cycles / hour.
AS12..S, ASL12..S,
Millions of ASL09..S, AS12..S, ASL12..S,
operating
cycles AS16..S, ASL16..S ASL09..S AS16..S, ASL16..S
AS09..S
4
3
2
6 13 57 9
1
0.6
0.5
9
7
5
0.3 9 3 1
7
5
3
0.2 9 1
7
5
3
0.1 1 13 57 9
2 3 5 9 10 20 30
Breaking current Ic (A)
Example:
Breaking current = 9 A.
On the opposite curve at intersection " " 9 A the corresponding value for the electrical durability is approximately 0.6 millions
operating cycles.
1SBC101946S0201
6/16 | ABB