E16DU, EF19, EF45 electronic overload relays – 0.10 to 45.0 A

         Technical data





         Technical diagram – Intermittent periodic duty
          (Op/h)  Trip class 10E    (Op/h)   Trip class 20E   (Op/h)   Trip class 30E
                                                               50
              a
          160   t   = 0.5 s                                        a
                                     80                        45   t   = 5 s
                                         a
          140                        70   t   = 2 s            40
          switching frequency      100   t   = 1 s  switching frequency      50   t   = 4 s  switching frequency      30   t   = 10 s
          120
                                                               35
                                     60
                                                               25
              a
           80
                                     40
                                                                   a
                                           a
                                                               20
           60
                                     30
              a
              t   = 1.5 s
                                           a
           40
                                                                    a
                                         a
                                                               10
              a
              t   = 3 s              20   a  t   = 8 s t   = 6 s  15   t   = 15 s
                                                                   a
           20                        10   t   = 10 s               t   = 20 s
              a
              t   = 5 s                 t   = 12 s              5   t   = 25 s
                                                                  a
                                        a
           0                   2CDC232001F0214  0         2CDC232002F0214           2CDC232003F0214
            0   20  40  60  80  100   (%)  0   20  40  60  80  100   (%)  0  0   20  40  60  80  100   (%)
                duty ratio                 duty ratio                duty ratio
         Trip class 10E            Trip class 20E            Trip class 30E
         Main circuit – Utilization characteristics according to UL/CSA
         Type                                         E16DU               EF19                 EF45
         Standards                                    UL 508, CSA 22.2 No. 14
         Maximum operational voltage                  600 V AC
         Trip rating                                  125% of FLA
         Full load amps (FLA)                         See table "Full load amps and short-circuit protective device"
         Short-circuit rating RMS symmetrical         See table "Full load amps and short-circuit protective device"  7
         Short-circuit protective device              See table "Full load amps and short-circuit protective device"
         Auxiliary circuit according to UL/CSA
         Type                                         E16DU               EF19                 EF45
         Contact rating                       N.C., 95-96 B600, Q300      B600, Q600
                                              N.O., 97-98 B600, Q300      B600, Q600
         Conventional free-air thermal current        6 A
         Full load amps and short-circuit protective device
         Type              Full load amps (FLA)  Short-circuit protective device
                                             480 V AC               600 V AC
                                             SCCR       Fuse type   SCCR        Fuse type  SCCR        Fuse type
         E16DU-0.32        0.32 A            50 kA      2 A, Class J  5 kA      2 A, K5 / RK5  100 kA  2 A, Class J
         E16DU-1.0         1.00 A            50 kA      2 A, K5 / RK5  5 kA     2 A, K5 / RK5  100 kA  2 A, Class J
         E16DU-2.7         2.70 A            50 kA      4 A, K5 / RK5  5 kA     4 A, K5 / RK5  100 kA  4 A, Class J
         E16DU-6.3         6.30 A            50 kA      15 A, K5 / RK5  5 kA    15 A, K5 / RK5  100 kA  15 A, Class J
         E16DU-18.9        18.90 A           50 kA      30 A, K5 / RK5  5 kA    30 A, K5 / RK5  100 kA  30 A, Class J

         Type              Full load amps (FLA)  Short-circuit protective device
                                             480 V AC               600 V AC
                                             SCCR       Fuse type   SCCR        Fuse type  SCCR        Fuse type
         EF19-0.32         0.32 A            50 kA      2 A, Class J  5 kA      2 A, K5 / RK5  100 kA  2 A, Class J
         EF19-1.0          1.00 A            50 kA      2 A, K5 / RK5  5 kA     2 A, K5 / RK5  100 kA  2 A, Class J
         EF19-2.7          2.70 A            50 kA      4 A, K5 / RK5  5 kA     4 A, K5 / RK5  100 kA  4 A, Class J
         EF19-6.3          6.30 A            50 kA      15 A, K5 / RK5  5 kA    15 A, K5 / RK5  100 kA  15 A, Class J
         EF19-18.9         18.90 A           50 kA      30 A, K5 / RK5  5 kA    30 A, K5 / RK5  100 kA  30 A, Class J

         Type              Full load amps (FLA)  Short-circuit protective device
                                             480 V AC               600 V AC
                                             SCCR       Fuse type   SCCR        Fuse type  SCCR        Fuse type
         EF45-30           30 A              18 kA      150 A, K5 / RK5  18 kA  150 A, K5 / RK5  100 kA  150 A, Class J
         EF45-45           45 A              18 kA      200 A, K5 / RK5  18 kA  200 A, K5 / RK5  100 kA  200 A, Class J