Page 17 - 1SBC100195C0203_Short_form_motor_protection_ control
P. 17

Time)
                                                                                                                               Time)
                                                                                                                               Time)














 Type  MS116  MS132  MS165  MS5100  MO132  MO165                MO5100                    MS132-T
 Thermal and electromagnetic protection  Yes  Yes  Yes  Yes  -  -  -                      Yes                       2
 Electromagnetic protection   -  -  -  -  Yes  Yes              Yes                       -
 Phase loss sensitivity  Yes  Yes  Yes  Yes  -  -               -                         Yes
 Switch position  ON/OFF  ON/OFF/TRIP  ON/OFF/TRIP  ON/OFF/TRIP  ON/OFF/TRIP  ON/OFF/TRIP  ON/OFF/TRIP  ON/OFF/TRIP
 Magnetic trip indication  -  Yes  Yes  Yes  -  -               -                         Yes
 Lockable handle without accessories  -  Yes  Yes  Yes  Yes  Yes  Yes                     Yes
 Disconnecting feature  Yes  Yes  Yes  Yes  Yes  Yes            Yes                       Yes
 Width  45 mm  45 mm  55 mm  90 mm  45 mm  55 mm                76.2 mm                   45 mm
 Rated operational current I e  0.16 ... 32 A  0.16 ... 32 A  16 ... 65 A  100 A  0.16 ... 32 A  16 ... 65 A  70 ... 100 A  0.16 ... 32 A
 Setting range  0.1 ... 32 A  0.1 ... 32 A  10 ... 65 A  40 ... 100 A   2)  -  -  -       0.1 ... 25 A
 Ambient air temperature  -25 ... +55 °C  1)  -25 ... +60 °C  1)  -20 ... +60 °C  1)  -25 ... +70 °C  -25 ... +60 °C  -25 ... +60 °C  -25 ... +70 °C  -25 ... +60 °C  1)
 1)  Compensated
 2)  For motor loads only up to 80 A
 Accessories
 Auxiliary contact  HKF1, HK1  AUX  HKF1, HK1                   AUX                       HKF1
 Signalling    for tripped alarm  SK1  AUX SA  SK1              -                         SK1
 contact  for short-circuit alarm  -  CK1  -  -                 -                         CK1
 Shunt trip  AA1  SOR-C  AA1                                    SOR-C                     AA1
 Undervoltage release  UA1  UVR-C  UA1                          UVR-C                     UA1
 Table for short-circuit ratings for 400/415 V
 Standard range  Performance range  Standard range  Performance range                    Transformer protection
 MS116  MS132, MS165, MS5100  MO132   MO132, MO165, MO5100                               MS132-T
 Selection parameters
 Rated operational  Setting range for   Type  Short-circuit    Type  Short-circuit    Type  Short-circuit    Type  Short-circuit    Type  Short-circuit
 power  thermal release  breaking capacity  breaking capacity  breaking capacity  breaking capacity  breaking capacity
 I CU  I  CS  I CU  I CS  I  CU  I CS                   I  CU           I CS                        I  / I CS
                                                                                                     CU
 0.03 kW 1)  0.1 … 0.16 A  MS116-0.16  50 kA  50 kA  MS132-0.16  100 kA  100 kA  MO132-0.16  100 kA  100 kA  MO132-0.16  100 kA  100 kA  MS132-0.16T  100 kA
 0.06 kW  0.16 … 0.25 A  MS116-0.25  50 kA  50 kA  MS132-0.25  100 kA  100 kA  MO132-0.25  100 kA  100 kA  MO132-0.25  100 kA  100 kA  MS132-0.25T  100 kA
 0.09 kW  0.25 … 0.4 A  MS116-0.4  50 kA  50 kA  MS132-0.4  100 kA  100 kA  MO132-0.4  100 kA  100 kA  MO132-0.4  100 kA  100 kA  MS132-0.4T  100 kA
 0.18 kW  0.4 … 0.63 A  MS116-0.63  50 kA  50 kA  MS132-0.63  100 kA  100 kA  MO132-0.63  100 kA  100 kA  MO132-0.63  100 kA  100 kA  MS132-0.63T  100 kA
 0.25 kW  0.63 … 1.0 A  MS116-1.0  50 kA  50 kA  MS132-1.0  100 kA  100 kA  MO132-1.0  100 kA  100 kA  MO132-1.0  100 kA  100 kA  MS132-1.0T  100 kA
 0.55 kW  1.0…1.6 A  MS116-1.6  50 kA  50 kA  MS132-1.6  100 kA  100 kA  MO132-1.6  100 kA  100 kA  MO132-1.6  100 kA  100 kA  MS132-1.6T  100 kA
 0.75 kW  1.6…2.5 A  MS116-2.5  50 kA  50 kA  MS132-2.5  100 kA  100 kA  MO132-2.5  100 kA  100 kA  MO132-2.5  100 kA  100 kA  MS132-2.5T  100 kA
 1.5 kW  2.5…4.0 A  MS116-4.0  50 kA  50 kA  MS132-4.0  100 kA  100 kA  MO132-4.0  100 kA  100 kA  MO132-4.0  100 kA  100 kA  MS132-4.0T  100 kA
 2.2 kW  4.0…6.3 A  MS116-6.3  50 kA  50 kA  MS132-6.3  100 kA  100 kA  MO132-6.3  100 kA  100 kA  MO132-6.3  100 kA  100 kA  MS132-6.3T  100 kA
 4.0 kW  6.3…10 A  MS116-10  50 kA  50 kA  MS132-10  100 kA  100 kA  MO132-10  100 kA  100 kA  MO132-10  100 kA  100 kA  MS132-10T  100 kA
 5.5 kW  8…12 A  MS116-12  25 kA  25 kA  MS132-12  100 kA  100 kA  MO132-12  100 kA  100 kA  MO132-12  100 kA  100 kA  MS132-12T  100 kA
 7.5 kW  10…16 A  MS116-16  16 kA  16 kA  MS132-16 / MS165-16  100 kA  100 kA  MO132-16  100 kA  100 kA  MO132-16 / MO165-16  100 kA  100 kA  MS132-16T  100 kA
 7.5 kW  14  ...  20 A  MS165-20  100 kA  100 kA  MO165-20  100 kA      100 kA
 7.5 kW  16…20 A  MS116-20  15 kA  10 kA  MS132-20  100 kA  100 kA  MO132-20  100 kA  100 kA  MO132-20  100 kA  100 kA  MS132-20T  100 kA
 11 kW  18 … 25 A  MS165-25  100 kA  100 kA
 11 kW  20…25 A  MS116-25  15 kA  10 kA  MS132-25  50 kA  50 kA  MO132-25  50 kA  50 kA  MO132-25 / MO165-25  50 kA / 100 kA  50 kA / 100 kA  MS132-25T  50 kA
 15 kW  25…32 A  MS116-32  10 kA  10 kA  MS132-32  50 kA  25 kA  MO132-32  50 kA  25 kA  MO132-32  50 kA  25 kA  Transformer protection:
                                                                                         The instantaneous short-circuit current
 15 kW  23  ...  32 A  MS165-32  100 kA  100 kA  MO165-32  100 kA       100 kA
                                                                                         setting is 20 times the rated operational
 22 kW  30  ...  42 A  MS165-42  50 kA  50 kA  MO165-42  50 kA          50 kA            current.
 22 kW  40  ...  54 A  MS165-54  50 kA  30 kA  MO165-54  50 kA          30 kA
 25 kW  -                             MO5100-70         36 kA           36 kA
 30 kW  52  ...  65 A  MS165-65  50 kA  30 kA  MO165-65  50 kA          30 kA
 37 kW  40 ... 100 A  MS5100-100  70 kA  70 kA  MO5100-80  36 kA        36 kA                                       2CDC131055C0201
 45 kW  40 ... 100 A  MS5100-100  70 kA  70 kA  MO5100-100  36 kA       36 kA
 1)  690 V

                                                                          ABB  Motor protection and control - short form catalog  |  2/9