Page 803 - Motor protection and control Manual motor starters, contactors and overload relays
P. 803

ABB  MOTOR PROTECTION AND CONTROL                                                10/15

          —

          HF0.6, HF2.4, HF9 electronic compact starters
          Technical diagrams




          Derating curve
          Please consider the derating curves for group mounting with and without ≥22.5 mm distance and the overload protection for
          tripping class 10A.

          Load
          current  (A)
                9
                                                            HF9
                8
                            HF9
                7
                6
                5
                4
                3                   HF2.4
                2
                1                   HF0.6
                0
                 0         10       20        30        40       50        60       70
                                                                             Ambient temperature  (°C)
                      With 22.5 mm distance
                      Side by side

          Derating curve HF range - electronic compact starters


          Tripping characteristics
        Tripping time  (s)

           10000.00


           1000.00

                                                                                                                      10
           100.00



            10.00



            1.00



            0.10
                1      2      3      4      5      6      7      8       9     10
                   Class10 A                                                Overcurrent factor
                   Class10 A +20 %
                   Class10 A -20 %
          Tripping characteristics class 10A HF range - electronic compact starters
   798   799   800   801   802   803   804   805   806   807   808