Page 158 - EPR Catalog 2015
P. 158

Thermistor motor protection relays
Ordering details - PTC temperature sensors C011

                                                   Description1SVC 110 000 F0531

                                                   The PTC temperature sensors (temperature-dependent with positive temperature coefficient)
                                                   are selected by the manufacturer of the motor depending on:
                                                   – the motor insulation class according to IEC/EN 60034-11,

2 – the special characteristics of the motor, such as the conductor cross-section of the wind-

                                                       ings, the permissible overload factor etc.
                                                   – special conditions prescribed by the user, such as the permissible ambient temperature,

                                                       risks resulting from locked rotor, extent of permitted overload etc.
                                                   One temperature sensor must be embedded in each phase winding. For instance, in case of
      Temperature sensor characteristics three-phase squirrel cage motors, three sensors are embedded in the stator windings. For
                                                   pole-changing motors with one winding (Dahlander connection), 3 sensors are also sufficient.
                                                   Pole-changing motors with two windings, however, require The sensors are suitable for em-
      RPTC bedding in motor windings with rated operating voltages of up to 600 V AC. Conductor length:
       [⏲] 500 mm per sensor. A 14 V varistor can be connected in parallel to protect the sensors from
       104 overvoltage. Due to their characteristics, the thermistor motor protection relays can also be
                                                   used with PTC temperature sensors of other manufacturers which comply with DIN 44 081
       103 and DIN 44 082 6 sensors.
                                                   If an additional warning is required before the motor is switched off, separate sensors for a
                                                   correspondingly lower temperature must be embedded in the winding. They have to be con-

            102

                                                   nected to a second control unit.

            101 TPTC [°C]
-20 °C
                         TNF - 20 K                                Ordering details  Color coding                     Type          Order code        Price     Weight
                                                                                                                                                      1 pce     (1 pce)
                             TNF - 5 K                              Rated response   white-brown                      C011-701)      GHC0110003R0001            kg (lb)
                                TNF                                 temperature TNF  white-white                      C011-801)      GHC0110003R0002
                                                                                     green-green                      C011-901)      GHC0110003R0003            0.02 (0.044)
                                   TNF + 5 K                       70 °C             red-red                          C011-1001)     GHC0110003R0004            0.02 (0.044)
                                      TNF + 15 K                   80 °C             brown-brown                      C011-1101)     GHC0110003R0005            0.02 (0.044)
                                               2CDC 252 068 F0208  90 °C             gray-gray                        C011-1201)     GHC0110003R0006            0.02 (0.044)
                                                                   100 °C            blue-blue                        C011-1301)     GHC0110003R0007            0.02 (0.044)
1) Temperature sensor C011, standard                               110 °C            white-blue                       C011-1401)     GHC0110003R0011            0.02 (0.044)
                                                                   120 °C            black-black                      C011-1501)     GHC0110003R0008            0.02 (0.044)
  version acc. to DIN 44081                                        130 °C            blue-red                         C011-1601)     GHC0110003R0009            0.02 (0.044)
2) Triple temperature sensor C011-3                                140 °C            white-green                      C011-1701)     GHC0110003R0010            0.02 (0.044)
                                                                   150 °C            black-black                      C011-3-1502)   GHC0110033R0008            0.02 (0.044)
                                                                   160 °C                                                                                       0.02 (0.044)
                                                                   170 °C                                                                                       0.05 (0.11)
                                                                   150 °C

                                                                   Technical data                                                   Sensor type C011

                                                                    Characteristic data                    50 -100 ⏲ at 25 °C

                                                                    Cold-state resistance                  10 000 ⏲
                                                                                                           <5s
                                                                    Warm-state resistance ± 5 up to 6 K    +180 °C
                                                                    of rated
                                                                    response temperature TNF
                                                                    Thermal time constant, sensor open 1)

                                                                    Permitted ambient temperature

                                                                     Rated response tempera-     PTC resistance R                   PTC resistance R2) at PTC temperatures of:
                                                                                                 from -20 °C to TNF
                                                                    ture Ȁ tolerance TNF Ȁ ͬTNF                           TNF - ͬTNF     TNF + ͬTNF                TNF + 15 K
                                                                                                         - 20 K       (UPTC ͨ 2.5 V)  (UPTC ͨ 2.5 V)            (UPTC ͨ 7.5 V)
                                                                   70 Ȁ5 °C
                                                                   80 Ȁ5 °C                      ͨ 100 ⏲              ͨ 570 ⏲         ͧ 570 ⏲                -
                                                                   90 Ȁ5 °C
                                                                   100 Ȁ5 °C                                          ͨ 550 ⏲         ͧ 1330 ⏲               ͧ 4000 ⏲
                                                                   110 Ȁ5 °C                                          ͨ 570 ⏲
                                                                   120 Ȁ5 °C                                                          ͧ 570 ⏲                -
                                                                   130 Ȁ5 °C
                                                                   140 Ȁ5 °C
                                                                   150 Ȁ5 °C
                                                                   160 Ȁ5 °C
                                                                   170 Ȁ7 °C

                                                                   1) Not embedded in windings.
                                                                   2) For triple temperature sensor take values x 3.

2/91 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210