Page 261 - EPR Catalog 2015
P. 261

CP-ASI range
Technical data

Type                                         CP-ASI/2.8                                              CP-ASI/4.0  CP-ASI/8.0        CP-ASI/4.0 DC/DC
General data
                                                                                                                                   typ. < 12.7 W
MTBF                                      on request                                                                               (24 V DC, 4.0 A)
                                                                                                                                   typ. 90.5 %
Power dissipation                         typ. < 9.1 W                               typ. < 13.5 W               typ. < 21.2 W     40 x 131 x 107 mm
                                                                                                                                   (1.58 x 5.16 x 4.21 in)
Efficiency                                (230 V AC, 2.8 A) (230 V AC, 4.0 A) (230 V AC, 8.0 A)                                    151 x 65 x 140 mm
Duty time                                                                                                                          (5.94 x 2.56 x 5.51 in)
Dimensions (W x H x D)                    typ. 90.5 %                                typ. 90 %                   typ. 92.0 %       0.488 kg (1.076 lb)
                                                                                                                                   0.750 kg (1.287 lb)
Weight                                    100 %
                                                                                                                                   -25...+70 °C
Material of housing                       product dimensions 49 x 131 x 107 mm 73 x 131 x 107 mm 91 x 131 x 107 mm                 -25...+60 °C
Mounting                                                                                                                           -40...+85 °C
Mounting position                         (1.93 x 5.16 x 4.21 in) (2.87 x 5.16 x 4.21 in) (3.58 x 5.16 x 4.21 in)
Minimum distance to other units                                                                                                    50 V
Degree of protection                   packaging dimensions 151 x 65 x 140 mm 151 x 98 x 140 mm 151 x 120 x 140 mm                 50 V                          3
Protection class
Electrical connection                     (5.94 x 2.56 x 5.51 in) (5.94 x 3.86 x 5.51 in) (5.94 x 4.72 x 5.51 in)                  1.5 kV 1.2/50 μs
                                                                                                                                   0.8 kV 1.2/50 μs
                                          net weight 0.495 kg (1.019 lb) 0.653 kg (1.440 lb) 0.897 kg (1.997 lb)                   500 V 1.2/50 μs
                                                                                                                                   1.5 kV AC /
                                          gross weight 0.568 kg (1.252 lb) 0.750 kg (1.653 lb) 1.015 kg (2.238 lb)                 1.5 kV AC
                                                                                                                                   1.5 kV AC /
                                          metal                                                                                    1.5 kV AC

                                          DIN rail (IEC/EN 60715), snap-on mounting without any tool                               input circuit:
                                                                                                                                   Level 3 (2 kV)
                                          horizontal                                                                               output circuit:
                                                                                                                                   Level 2 (1 kV)
                                          horizontal / vertical 15 mm / 25 mm (0.59 / 0.99 in)                                     input circuit: L-L Level 2
                                                                                                                                   (1 kV) / L-PE Level 3 (2 kV)
                                          housing / terminals IP20 / IP20                                                          output circuit:
                                                                                                                                   Level 1 (0.5 kV)
                                          I                                                                                        Level 3 (10 V, 150
                                                                                                                                   kHz - 80 MHz)
Wire size                        fine-strand with wire end ferrule 0.5-4 mm² (20-12 AWG)
                                 fine-strand without wire end ferrule 0.5-4 mm² (20-12 AWG)                                        IEC/EN 61000-6-3
Stripping length
Tightening torque                                                      rigid 0.5-6 mm² (20-10 AWG)                                 -
                                                                                7 mm (0.28 in)
                                                                                0.8 Nm (7.08 lb.in)

Environmental data

Ambient temperature range                                   operation -10...+70 °C
                                                           rated load -10...+60 °C
Vibration (sinusoidal)
(IEC/EN 60068-2-6)                                            storage -25...+85 °C
                                                                           2-17.8 Hz, amplitude ± 1.6 mm

                                       sinusoidal (IEC/EN 60068-2-6) 17.8 Hz - 500 Hz, 2 g

                                       random (IEC 60068-2-64) 2-800 Hz 0.5 s² (s³)

Shock (half-sine) (IEC/EN 60068-2-27)     15 g (6 ms), 10 g (11 ms)

Isolation data

Rated insulation voltage Ui            input circuit / output circuit 300 V
(IEC/EN 60950-1, EN 50178)                                 input / PE 300 V

Rated impulse withstand voltage Uimp                     output / PE 50 V
(EN 50178)                                           shield / output 50 V
Power-frequency withstand voltage
test (test voltage) (routine test /                       shield / PE 50 V
type test)                                            input / output 6 kV 1.2/50 μs

                                                           input / PE 4 kV 1.2/50 μs
                                                         output / PE 500 V 1.2/50 μs
                                                      input / output 2.5 kV AC / 3.0 kV AC

                                                           input / PE 2.5 kV AC / 2.5 kV AC

Pollution degree (IEC/EN 60950-1)         output / PE 500 V AC / 500 V AC
Overvoltage category (UL/IEC/EN 60950-1)                    2

                                                   input II (IEC/EN 60950-1), III (EN 50178)
                                                output II (IEC/EN 60950-1), II (EN 50178)

Standards                                                             2006/95/EC
                                                                      2004/108/EC
Low Voltage Directive                                                 2011/65/EC
EMC directive                                                         IEC/EN 60950-1
RoHS directive                                                        SELV (IEC/EN 60950-1), PELV
Electrical safety
Protective low voltage                                                IEC/EN 61000-6-2
                                          IEC/EN 61000-4-2 Level 4 (8 kV / 15 kV)
Electromagnetic compatibility

Interference immunity to
electrostatic discharge

radiated, radio-frequency,                IEC/EN 61000-4-3 Level 3 (10 V/m)
electromagnetic field                     IEC/EN 61000-4-4 input circuit: Level 4 (4 kV)
electrical fast transient/burst

                                          output circuit: Level 3 (2 kV)

surge                                     IEC/EN 61000-4-5 input circuit: L-L Level 3 (2 kV) / L-PE Level 4 (4 kV)

                                          output circuit: Level 1 (0.5 kV)

conducted disturbances, induced by          IEC/EN 61000-4-6 Level 3 (10 V, 150 kHz - 80 MHz)                    IEC/EN 61000-6-4
radio-frequency fields                                                                                           -
voltage dips, short interruptions and      IEC/EN 61000-4-11 Class 3
voltag variations
Interference emission                                                    IEC/EN 61000-6-3
high-frequency radiated                IEC/CISPR 22, EN 55022 Class B
high-frequency conducted               IEC/CISPR 22, EN 55022 Class B
limits for harmonic current emissions
                                            IEC/EN 61000-3-2 Class A

                                                 2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 3/62
   256   257   258   259   260   261   262   263   264   265   266