Page 98 - Kabeldon
P. 98

Technical data






        Busbar system                    Quantity    400 A      630 A    1000 A  1600 A  1600 A  2500 A
                                                                                      CSS  2)  CSS  2)
        Rated operational voltage, U e   V           690         690      690   690    690    690
        Rated insulation voltage, U      V          1000        1000     1000   1000   1000   1000
                       i
        Rated operational current,  I   e  A         400         630     1000   1600   1600   2500
        and rated conventional thermal current, I th
        Rated short-time withstand current, I    kA  rms/s  30/0.2 1)  23/1     40/1 1)  70/1 1)  30/1  65/1
                                                                   1)
                             cw
        Rated fused short-circuit current, I  kA  50    85    50    85     –     –      –      –
                           cf              rms
                                         max A   3//315  3//250  3//315  3//250  –  –   –      –
        Rated peak withstand current, I pk  kA  peak  55         55        –     –     67     148
        Rated peak withstand current; 1 m long busbar without  kA  peak  –   –  50  85  –      –
        fitted device, I
                pk
        Degree of protection according to IEC 60 529  IP2X      IP2X      IP2X  IP2X   IP2X   IP2X
        1) Test prerequisite: DT=100 K. Final temperature of the busbar max. 150° C.
        2) Adjusted for use in substations and low voltage switchgears.
   5   Switching device with    Quan-   SLD 000  SLD-FHD   SLD 00  SLD-FHD    SLD 1         SLD 2        SLD   FD
       dependent manual operation,    tity       000                 00                                  63   3300
       uninterrupted duty
       Rated operational voltage, U  V  400  690  1)  230  400  690  1)  230  400  690   1)  400  690  1)  1000   1)  400  400
                       e
       Rated insulation voltage, U i  V  690     690       690       690      690            1000        690  690
       Rated impulse withstand voltage,   kV  8   8         8        8         8              8          8     8
       U imp
       Rated operational current, I     A  100  80  100  160  160    160   250   250   400   355   100   63   400
                       e
       and rated conventional thermal                                      400  3)     630  3)
       current, I   2)
             th
       Utilization category according   AC-23B  AC-22B  AC-21B  AC-23B  AC-21B  AC-21B  AC-23B  AC-22B  AC-23B AC-22B AC-21B  AC-21B
       to IEC 60947-3
       Rated short-time withstand   kA rm/s  6.1/1  5)  –  6.1/1   5)  –     16.2/1  5)     16.2/1  5)   –    15/1
       current, I
             cw
       Rated peak withstand current, I  kA  10.9   5)  –  10.9   5)  –       34.4    5)     34.4   5)    –     42
                         pk   peak
       Rated conditional fused   kA rms  50  30  30     50    30     30     50    50    50   50    30    40    50
       short-circuit current, I
                    cf      max A   100   80     100    160   160    160   250   250   400   355   100   63   2//400
       Degree of protection according to   fuse  IP2X  4)  IP2X  4)  IP2X  4)  IP2X  4)  IP2X  IP2X      IP2X  IP2X
       IEC 60529
       Connectable conductor cross-  mm 2  2.5-95  2.5-95  2.5-95   2.5-95   50-300         50-300      1,5–25 50-300
       section, Al/Cu
       Remarks
       1) To be used only in dry environments.
       2) Fuse with power dissipation according to IEC 60269-2-1.
       3) With linking knives.
       4) IP1X at operation, depending on design dimensions of the fuse.
       5) Tested with the earthing device JDD.
        Switching device with dependent    Quantity  SLDL 2     SLDL 2-1P          SLDL 3           SLDL 3-1P
        manual operation, uninterrupted duty
        Rated operational voltage, U e  V  400  690   1)  1000   1)  230  400  1)  690   1)  400  690  1)  1000  1)  230  400  1)  690  1)
        Rated insulation voltage, U  V         1000              1000               1000              1000
                       i
        Rated impulse withstand voltage, U imp  kV  8              8                 8                  8
        Rated operational current, I  and   A  400  400  100  400  400  100   630   500   100   630    500   100
                       e
        rated conventional thermal current, I   2)
                             th
        Utilization category according to    AC-23B  AC-22B  AC-21B  AC-23B  AC-22B  AC-21B  AC-23B  AC-22B  AC-21B  AC-23B  AC-22B  AC-21B
        IEC 60947-3
        Rated short-time withstand current, I    kA /s  10,3/1   10,3/1            10,3/1             10,3/1
                             cw      eff
        Rated peak withstand current, I  kA    21,0               21,0              21,0              21,0
                          pk         topp
        Rated conditional fused short-circuit   kA eff  50  50  28   50  50  28  50  50    28     50   50    28
        current, I cf            max A   400   400    100    400  400   100   630   500   100    630   500   100
        Degree of protection according to      IP2X               IP2X              IP2X              IP2X
        IEC 60529
        Connectable conductor cross-section,   mm 2  35-240      35-240            35-240             35-240
        Al/Cu                                2 x 95-240         2 x 95-240        2 x 95-240        2 x 95-240
        Remarks
        1) To be used only in dry environments.
        2) Fuse with power dissipation according to IEC 60269-2-1.

       5/3  | 2016 |  Kabeldon fusegear and cable distribution cabinets | Technical data |
   93   94   95   96   97   98   99   100   101   102   103