Page 480 - Residentiel
P. 480
Coordination des protections
Filiation
MCB - MCB @ 240 V Amont S200 S200M S200P
B-C B-C B-C
NRS T NF Courbe Icu [kA] @ 240 V 20 25
Aval In [A] 0.5..63 40 25
20 0.5..63 0.5..25 32..63
S20X4T3 S202 6 2..40 20 25
10 2..40 25 40 25
SN201L C 20 0.5..63 25 40 25
SN201 C,D 25 0.5..63 40 25
N201L S200 B,C,K,Z 40 0.5..25 40
S200M B,C 25 32..63
SN201L
S200P B,C,
D,K,Z
N SN201L=DS201L, SN201=DS201=DS202C
MCB (S800) - MCB (SN201&S200) @ 240 V
Amont S800C S800N S800S
B, C, D B, C, D, K
Courbe B, C, D
36 50
Aval Icu [kA] @ 240 V 25 40, 50 63 40, 50 63
In [A] 25..50 63 80..125 25, 32 25 18 80..125 25 32 25 18 80..125
36 36 15 50 40 50 15
SN201L C 6 2..40 25 18 15 36 50
36 50
SN201 C,D 10 2..40 25 36 50
36 50
S200L C 6 2..40 25 36 50
S200 B,C,K,Z 10 0.5..63 25
S200M B,C 15 0.5..63 25
S200P B,C, 25 0.5..25 25
D,K,Z 15 32..63 25
SN201L=DS201L, SN201=DS201=DS202C
MCCB @ 415 V - MCB @ 240 V
Amont * XT1 XT2 XT3 XT1 XT2 XT3 XT1 XT2
LV
NRS T Version B C N SH
XT3 120 150
Aval Courbe In [A] Icu [kA] 18 25 36 50 70 20 20
SN201L 18 18
N SN201L C 2..25 6 18 18 18 20 18 20 18 20 25 25
10 10 18 18
32, 40 10 10 10 18 10 18 10 18
2..25 25 25 25
SN201 C 10 18 18 18 18 18 18 18
32, 40 18 18 18
* Disjoncteur en amont 4p (circuit en aval entre une phase et le neutre)
SN201L=DS201L, SN201=DS201=DS202C
MCB - MCB @ 415 V
RS T RS T NRS T NRS T NRS T
S204 S204 S204
S203 S203
S203 S202 S204 S202 S202
Amont S200 S200M S200P S800N S800S
Courbe B-C B-C B-C B-C-D B-C-D-K
Aval Icu [kA] 10 15 25 15 36 50
In [A] 0.5..63 0.5..63 0.5..25 32..63 10..125 10..125
S200 B,C,K,Z 10 0.5..63 15 25 15 36 50
S200M B,C 15 0.5..63 25 36 50
8 S200P B,C, 25 0.5..25 36 50
D,K,Z 15 32..63 36 50
S800N B,C,D 36 10..125
S800S B,C,D,K 50 10..125
8/14 | ABB Résidentiel et petit tertiaire