DOL and reversing starters protected by overload relays

       With AF contactors - Open type version in kit form





                                  Application
                                  Full voltage direct-on-line and reversing starting for controlling three-phase asynchronous motors is a simple
                                  and economic solution characterised by a high starting torque (1.9 to 2.1 times full-speed torque) and a
                                  starting current 5.5 to 7 times nominal current.
                                  I  C
                                  /In  /Cn
                                  7
                                  6           I
                   1SBC100058V0014  5 4                     I = current
                                                            C = torque
                                  3                         In = nominal current
                                                            Cn = nominal torque
       AF09-30-10 + TF42
                                  2
                                          C
                                  1
    5                             0  10  30    60  80  100



                                  Coordination Types
                                  The contactor, the short-circuit protection device and the thermal overload relay control and protect motors
                                  against overload and short-circuits according to coordination types 1 and 2 (IEC 60947-4-1 / EN 60947-4-1)
                                  defining the anticipated level of service continuity as follow:
                      1SFC101153V0001  Type 1: In short-circuit conditions, the contactor or starter does not endanger persons or installations and
                                  will not be able to then operate without being repaired or having parts replaced.
                                  Type 2: In short-circuit conditions, the contactor or starter does not endanger persons or installations and
                                  will be able to operate afterwards. The risk of contacts light welding is acceptable.
       AF140-30-11 + TF140DU



                                  Main Technical Data
                                  Standards                       IEC 60947-4-1 / EN 60947-4-1
                                  Rated operational voltage Ue max.  690 V - 50/60 Hz
                                  Rated insulation voltage Ui
                                    acc. to IEC 60947-4-1         690 V
                                    acc. to UL / CSA              600 V
                                  Ambient air temperature
                                    Close to the device           ≤ 60 °C (TF42: 38 A above ≤ 50 °C)
                                  Degree of protection            IP20
                        1SBC100059V0014  Switching frequency      Refer to "Switching frequency diagrams" page




       AF09-30-10 + BER16-4 + VEM4
       + TF42







                                  Mounting positions


                              1SFC101152V0001





       AF140-30-11 + BER140-4 + VM19   Pos. 1           Pos. 1                                                    1SBC101920S0201
       + TF140DU                  Direct-on-line       Reversing

       5/40  |  ABB