Page 414 - Motor_protection_and_control_Manual_motor_starters_ contactors
P. 414
EK550, EK1000 4-pole contactors
800 to 1000 A AC-1
AC operated - with 1 N.O. + 1 N.C. auxiliary contacts
Description
EK550 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads (i.e. resist-
ance furnaces...) and generally for controlling power circuits up to 1000 V AC and 600 V DC, EK1000 up to
1000 V AC.
These contactors are of the block type design with:
– 4 main poles
1SFC98099-069 – control circuit: AC operated
– add-on auxiliary contact blocks for side mounting and a wide range of accessories.
Ordering details
EK1000-40-11 IEC UL/CSA Rated control circuit Auxiliary Type Order code Weight
Rated operational General use voltage contacts
current rating Uc fitted Pkg
θ ≤ 40 °C 600 V AC (1) (1 pce)
AC-1
5 A A V 50 Hz V 60 Hz kg
800 540 48 - 1 1 EK550-40-11 SK827041-AD 17.200
110 110…120 1 1 EK550-40-11 SK827041-EF 17.200
110…115 115…127 1 1 EK550-40-11 SK827041-EG 17.200
220 220…240 1 1 EK550-40-11 SK827041-EL 17.200
220…230 230…255 1 1 EK550-40-11 SK827041-EM 17.200
400…415 - 1 1 EK550-40-11 SK827041-AR 17.200
1000 - 48 - 1 1 EK1000-40-11 SK827044-AD 17.500
110 110…120 1 1 EK1000-40-11 SK827044-EF 17.500
110…115 115…127 1 1 EK1000-40-11 SK827044-EG 17.500
220 220…240 1 1 EK1000-40-11 SK827044-EL 17.500
220…230 230…255 1 1 EK1000-40-11 SK827044-EM 17.500
400…415 - 1 1 EK1000-40-11 SK827044-AR 17.500
(1) Other control voltages see voltage code table.
Main dimensions mm, inches
11 0.43" 1) 270 10.63" 11 0.43" 1)
244 9.61" 225.5 8.88"
11 0.43" 1) 270 10.63" 11 0.43" 1) ø 11 0.43" 2) 139.5 5.49" 8 0.31"
244 9.61" 23 0.91" 4)
ø 11 0.43" 2) 225.5 8.88" (M10) 5)
139.5 5.49" 6 0.24"
23 0.91" 4) (M10) 5)
1/L1 3/L2 5/L3 7/L4
1/L1 3/L2 5/L3 7/L4 299 11.77" 223 8.78"
272 10.71"
2/T1 4/T2 6/T3 8/T4 223 8.78" 2/T1 4/T2 6/T3 8/T4
40 3) E1694D
1.57"
0.79"
20
67 25 12.5 E0263D6 11 40 3) E0264D6 67 40 E1692D 11
2.64" 0.98" 0.49" 1.57" 2.64" 1.57"
EK550 EK1000
1) Dimension for extra auxiliary contact block.
2) Screw, nut and washer by-packed.
3) Min. distance to uninsulated wall. 1SFC101217C0201
4) Damping elements are included.
5) Earthing screw.