Page 36 - Motor protection and control Manual motor starters, contactors and overload relays
P. 36
2/10 ABB MOTOR PROTECTION AND CONTROL
—
MS116 manual motor starters
0.10 to 32 A – with thermal and electromagnetic protection
02
MS116 is a compact and economic range for motor protection up to 15 kW (400 V) / 32 A in width
of 45 mm. Further features are the built-in disconnect function, temperature compensation,
trip-free mechanism and a rotary handle with a clear switch position indication. The manual
motor starter is suitable for three- and single-phase applications. Auxiliary contacts, signaling
contacts, undervoltage releases, shunt trips, power in-feed blocks and locking devices for pro-
tection against unauthorized changes are available as accessory. These are suitable
2CDC241004V0017 Rated Setting range Short-circuit Rated Type Order code Weight
throughout the MS116/MS132/MS165-range.
operational
capacity Ics
short-circuit
power breaking instantaneous (1 pce)
400 V at 400 V AC current
MS116-16
AC-3, AC-3e setting li
kW A kA A kg
0.03 (1) 0.10 ... 0.16 50 2.00 MS116-0.16 1SAM250000R1001 0.225
0.06 0.16 ... 0.25 50 3.10 MS116-0.25 1SAM250000R1002 0.225
0.09 0.25 ... 0.40 50 5.00 MS116-0.4 1SAM250000R1003 0.225
0.18 0.40 ... 0.63 50 7.90 MS116-0.63 1SAM250000R1004 0.225
0.25 0.63 ... 1.00 50 12.5 MS116-1.0 1SAM250000R1005 0.225
0.55 1.00 ... 1.60 50 20.0 MS116-1.6 1SAM250000R1006 0.265
2CDC241017V0017 1.50 2.50 ... 4.00 50 50.0 MS116-4.0 1SAM250000R1008 0.265
1.60 ... 2.50
31.3
1SAM250000R1007
0.75
0.265
50
MS116-2.5
50
78.8
MS116-6.3
1SAM250000R1009
0.265
4.00 ... 6.30
2.20
1SAM250000R1012
180
MS116-12
8.00 ... 12.0
5.50
25
0.265
MS116-25 4.00 6.30 ... 10.0 50 150 MS116-10 1SAM250000R1010 0.265
7.50 10.0 ... 16.0 16 240 MS116-16 1SAM250000R1011 0.265
7.50 16.0 ... 20.0 10 300 MS116-20 1SAM250000R1013 0.310
11.0 20.0 ... 25.0 10 375 MS116-25 1SAM250000R1014 0.310
15.0 25.0 ... 32.0 10 480 MS116-32 1SAM250000R1015 0.310
Mounted Auxiliary Contacts 1 N.O. + 1 N.C.
0.03 (1) 0.10 ... 0.16 50 2.00 MS116-0.16-HKF1-11 1SAM250005R1001 0.240
2CDC241019V0017 0.09 0.25 ... 0.40 50 5.00 MS116-0.4-HKF1-11 1SAM250005R1003 0.240
MS116-0.25-HKF1-11
3.10
0.16 ... 0.25
1SAM250005R1002
50
0.240
0.06
0.240
7.90
MS116-0.63-HKF1-11
50
0.18
1SAM250005R1004
0.40 ... 0.63
0.25
50
20.0
0.55 0.63 ... 1.00 50 12.5 MS116-1.0-HKF1-11 1SAM250005R1005 0.240
1SAM250005R1006
1.00 ... 1.60
MS116-1.6-HKF1-11
0.280
MS116-0.16-HKF1-11 0.75 1.60 ... 2.50 50 31.3 MS116-2.5-HKF1-11 1SAM250005R1007 0.280
1.50 2.50 ... 4.00 50 50.0 MS116-4.0-HKF1-11 1SAM250005R1008 0.280
2.20 4.00 ... 6.30 50 78.8 MS116-6.3-HKF1-11 1SAM250005R1009 0.280
4.00 6.30 ... 10.0 50 150 MS116-10.0-HKF1-11 1SAM250005R1010 0.280
5.50 8.00 ... 12.0 25 180 MS116-12.0-HKF1-11 1SAM250005R1012 0.280
7.50 10.0 ... 16.0 16 240 MS116-16.0-HKF1-11 1SAM250005R1011 0.280
7.50 16.0 ... 20.0 10 300 MS116-20-HKF1-11 1SAM250005R1013 0.326
MS116-25-HKF1-11
1SAM250005R1014
0.326
20.0 ... 25.0
11.0
375
10
2CDC241020V0017 15.0 25.0 ... 32.0 10 480 MS116-32-HKF1-11 1SAM250005R1015 0.326
Note: Manual motor starters should always be selected so that the actual motor current is within the setting range.
(1) 690 V
MS116-32-HKF1-11
79.9 3.15"
69.8 2.75"
80.1 3.15" 1.5 0.06" 5.5 0.22" 43.3 1.7"
1.5 0.06" 70 2.76"
5.5 0.22" 43.5 1.71"
0.07" 0.07" 1.7
3.54" 1.7 2.95" 1.38" 1.77" 2.3" 3.85" 2.95" 1.38" 1.77" 2.3"
90 1.1" 75 35 45 57.8 97.8 1.1" 75 35 45 57.8
27.5 27.5
2CDC131062C0201 - Rev. B
14 0.55" 14 0.55" 14 0.55" 14 0.55"
45 1.77" 45 1.77"
MS116 ≤ 16 A & MS116-HKF1-11 ≤ 16 A MS116 ≥ 20 A & MS116-HKF1-11 ≥ 20 A
Main dimensions mm, inches