Page 100 - 1SBC104119C0202_MainCatalog_R contactors
P. 100

AM-CC-JORE4500 and
AMF-CC-JORE4500 alternator field discharge contactors
Technical data

N.O. main pole - Utilization characteristics

Types                                       Single tripping coil AM-CC-JORE4500-21

                                            Double tripping coil                                 AMF-CC-JORE4500-21

Number of N.O. poles in series                                    2

Rated operational voltage Ue                                      750 V DC

Maximum breaking voltage                                          1500 V DC

Conventional free-air thermal current Ith

Open contactors                                θ ≤ 40 °C 4500 A
With conductor cross-sectional area                         4000 mm²

Ie / Rated operational current                 θ ≤ 40 °C          4500 A
Rated short-time withstand current Icw         θ ≤ 50 °C          4100 A
at 40 °C ambient temperature,                                     28000 A
in free air from a cold state                         1s          21000 A
                                                                  12000 A
                                                     10 s

                                                     30 s

                                               1 min 8000 A

5 Maximum breaking capacity at Ue              15 min 5000 A
      (L / R ≤ 15 ms)                           550 V 25000 A
                                                750 V 22000 A

                                               1000 V 20000 A

                                               1 500 V 10000 A

                                               2 250 V -

Maximum making capacity                                           32000 A

Dynamical withstand of pole                                       32000 A

Impedance per pole                                                0.04 mΩ

N.C. de-energisation pole - Utilization characteristics

Types                                        Single tripping coil AM-CC-JORE4500-21
                                            Double tripping coil
                                                                                                 AMF-CC-JORE4500-21

Number of N.C. de-energisation pole                               1

Conventional free-air thermal current Ith

Open contactors                                θ ≤ 40 °C 1000 A
With conductor cross-sectional area                         500 mm²

Maximum making capacity                                           9000 A

Rated short time current                       0.5 s 10000 A

                                               15 s 6000 A

Maximum breaking capacity at Ue                                   No breaking capacity

Impedance per pole                                                0.18 mΩ

General technical data

Types                                       Single tripping coil  AM-CC-JORE4500-21

                                            Double tripping coil  8 kV                           AMF-CC-JORE4500-21
                                                                  5500 V AC 50 Hz
Rated impulse withstand voltage Uimp.

Dielectric test voltage / 1 min

Ambient air temperature close to contactor

Operation in free air                                             -20…+55 °C
                                                                  -20…+80 °C
Storage                                                           Standard version for industrial environment and atmospheres
                                                                  2000 m
Climatic withstand

Maximum operating altitude (without derating)

Mechanical durability

Number of operating cycles                                        200000 cycles

Construction characteristics

Types                                       Single tripping coil  AM-CC-JORE4500-21

                                            Double tripping coil                                 AMF-CC-JORE4500-21
                                                                                                 2 N.O. + 2 N.C.:
Standard combination of auxiliary contacts                        3 N.O. + 2 N.C.:               2 CA15-F (N.O.)
                                                                  3 CA15-F (N.O.)                + 2 CA15-O (N.C.)
Maximum number of auxiliary contacts                              + 2 CA15-O (N.C.)     20       16                            1SBC104111S0201
Fixing dimensions (F)                                             5                     1200 mm  1200 mm
                                                                  1100 mm
Width                                                                                   1290 mm  1290 mm
Weight                                                            1190 mm               136 kg   137 kg
                                                                  135 kg

5/48 | ABB R contactors