Page 234 - EPR Catalog 2015
P. 234

CP-T range
Technical data

Data at Ta = 25 °C, Uin = 3 x 400 V AC and rated values, unless otherwise indicated

        Type                                                                 CP-T 24/5.0  CP-T 24/10.0 CP-T 24/20.0             CP-T 24/40.0
        Input circuit
        Rated input voltage Uin                                                                       L1, L2, L3              1.72 A
        Input voltage range                                                                                                   1058 W
                                                                3 x 400-500 V AC                                              30 A
        Frequency range AC                                                                                                    min. 15 ms
        Typical input current                                   340-575 V AC                                                  T 5 A / 500 V AC

3 Typical power consumption                                     480-820 V DC
        Inrush current limiting
        Power failure buffering time                            47-63 Hz
        Internal input fuse
        Recommended backup fuse                                 0.36 A                    0.65 A         1.1 A
        Power factor correction (PFC)
        Discharge current                                       135 W                     270 W          538 W

                                                                10 A                      20 A

                                                                min. 20 ms

                                                                per phase 2 A / 600 V AC                 T 3.15 A / 500 V AC

                                                                3 pole miniature circuit breaker ABB Type S203

                                                                Yes, passive

                                                                towards PE < 3.5 mA

                                                         input / output < 0.25 mA

Indication of operational states        OUTPUT OK: green LED output voltage OK
Output voltage                           OUTPUT LOW: red LED output voltage too low

Output circuit                                                                                     L+, L+, L-, L-
Rated output voltage
                                                                24 V DC

Tolerance of the output voltage                                 0...+1 %

Adjustment range of the output voltage                          22.5-28.5 V DC

Rated output power                                              120 W                     240 W          480 W                960 W

Rated output current Ir                                         Ta d 60 °C 5 A            10 A           20 A                 40 A
Derating of the output current                                                                                                3.5 %/°C
                                                         60 °C < Ta ≤ 70 °C 2.5 %/°C
Signalling contact
for output voltage OK                                           13-14 solid state (max. 60 V DC, 0.3 A)

                                                                Threshold 17.6-19.4 V

                                                         Insulation voltage 500 V DC

Mininum fuse rating to achieve short-circuit protection         13-14 ͧ 60 V DC, ͨ 0.3 A fast-acting

Maximum deviation with                                   load change statical ±1 %        ±1 % (single mode)

                                                                - ±5 % (parallel mode)

Control time                                  change of output voltage ± 0.5 %
                                        within the input voltage range

                                                            at nominal load < 2 ms

Starting time after applying                                          at Ir max. 1 s
the supply voltage                                       with 3500 μF max. 1.5 s

Rise time                                                at nominal load max. 150 ms

                                                         with 3500 μF max. 500 ms

Fall time                                                       max. 150 ms

Residual ripple and switching peaks                      BW = 20 MHz 100 mV                                                   80 mV

Parallel connection                                             not supported             configurable, to increase power, up to increase power,
                                                                                          to 2 devices, min. 0.1 Ir - max 0.9 Ir) up to 2 devices,

                                                                                                                                              min. 0.1 Ir - max.
                                                                                                                                              0.9 Ir use active
                                                                                                                                              current balancing

Series connection                                               not supported             yes, to increase voltage, max. 2 devices
Resistance to reverse feed                                      approx. 35 V
Output circuit - No-load, overload and short-circuit behaviour
Characteristic curve of output                                  combined U/I characteristic curve U/I- or Hiccup- hiccup / fold

Short-circuit protection                                        and hiccup mode                          mode adjustable back behavior
Short-circuit behaviour
Overload protection                                             continuous short-circuit proof
No-load protection
Overtemperature protection                                      current limiting
Starting of capacitive loads
                                                                hiccup mode

                                                                continuous no-load stability

                                                                yes, automatic recovery after temperature went down

                                                                3500 μF                   7000 μF        7000 μF              7000 μF