Page 348 - EPR Catalog 2015
P. 348

Interface relays R600 range
Technical data

Technical data

                                                                                         RB... 121 / RB... 121A low level

Input circuit                                  5 V DC           12 V DC           24 V AC/DC  48 V AC/DC  60 V AC/DC       115 V AC/DC 230 V AC/DC
                                                                                                                                               -15 %, +10 %
Rated control supply voltage Us                DC -15 %, +20 %                                0.33 W      0.54 W
                                                                                              7 mA        9 mA
Rated control supply voltage Us                AC -                               -/+ 10 %    8V          8V
tolerance
Rated frequency                                - 50/60 Hz
Typical power consumption
Typical current                                0.2 W            0.2 W             0.24 W                                   0.46 W        0.8 W
Drop-out voltage                                                                                                           4 mA          3.5 mA
Indication of operational states               40 mA            16 mA             10 mA                                    17 V          27 V

                                               1.2 V            2.2 V             4.5 V

                                            green LED V: control supply voltage applied

Output circuit

Kind of output                              11-12/14 relay, 1 c/o (SPDT) contact

Rated operational voltage Ue (IEC/EN 60947-1)  250 V AC

Minimum switching voltage                      5V

Maximum switching voltage                      250 V AC

5 Minimum switching current                    1 mA
        Rated free air thermal current Ith     6A

Rated operational      AC-12 (resistive) 230 V 6 A

current                AC-15 (inductive) 230 V 1.5 A

(IEC/EN 60947-5-1)     AC-15 (inductive) 120 V 3 A

                         DC-12 (resistive) 24 V 6 A

                         DC-13 (inductive) 24 V 1 A

                       DC-13 (inductive) 120 V 0.2 A

                       DC-13 (inductive) 230 V 0.1 A

AC rating          Utilization category (pilot duty) B300

(UL 508;

NEMA ICS-5)

DC rating          Utilization category (pilot duty) R300
(UL 508;
NEMA ICS-5)

Minimum switching power                        0.05 W / 0.05 VA
Mechanical lifetime
Electrical lifetime                            1 x 107 switching cycles
Response time
Release time                                at AC-15 1 x 105 switching cycles

                                               5 ms             5 ms              5 ms        5 ms        5 ms             6 ms          7 ms
                                                                                  8 ms        8 ms        8 ms             15 ms         16 ms
                                               8 ms             8 ms

Dimensions and weight                                      RB 121 / RB 121A low level                     RBR 121 / RBR 121 A low level

Weight                                net weight 0.02 kg (0.044 lb)                           6 x 75 x 75 mm (0.236 x 2.95 x 2.95 in)
Dimension                  product dimension 6 x 70 x 75 mm (0.236 x 2.76 x 2.95 in)

5/41 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210