184              MAIN CATALOG PLC AUTOMATION




          —
          AC500-XC
          Technical data




          PROFIBUS-DP modules
          Type                              CI541-DP-XC                       CI542-DP-XC
          Communication Interface
          Protocol                          PROFIBUS DP (DP-V0 and DP-V1 slave)
          ID configuration                  Per rotary switches on front face from 00h to FFh
          Field bus connection on terminal units  Sub-D 9 poles on TU510-XC or TU518-XC with baud rate up to 1MBaud
          Number of Channels per Module
          Digital            inputs         8                                 8
                             outputs        8                                 8
          Analog             inputs         4                                 –
                             outputs        2                                 –
          Digital configurable channels DC    –                               8
          (configurable as inputs or outputs)
          Additional configuration of channels as
          Fast counter (onboard I/O)        Configuration of max. 2 DI channels per module
          Occupies max 1 DO or DC when used as counter                       
          Connection
          Local I/O extension               
          Max. number of extension modules  max. 10 x S500 extension modules, fast counter from digital I/O modules can be also used
          Via terminal base TU5xx                                            
          Digital inputs
   05
          Input    signal voltage           24 V DC
                   characteristic acc. to EN 61132-2  Type 1
          0 signal                          -3...+5 V DC
          Undefined signal state            5...15 V DC
          1 signal                          15...30 V DC
          Residual ripple, range for  0 signal  -3...+5 V DC
                             1 signal       15...30 V DC
          Input time delay (0 -> 1 or 1 -> 0)   8 ms typically, configurable from 0.1 up to 32 ms
          Digital outputs
          Transistor outputs 24 V DC, 0.5 A  
          Readback of output                –                                  (on DC outputs)
          Outputs, supplied via process voltage UP  
          Switching of 24 V load            
          Output voltage at signal state 1   Process voltage UP - 0.8 V
          Output current
          Nominal current per channel       500 mA at UP = 24 V DC
          Maximum (total current of all channels)   8 A
          Residual current at signal state 0   < 0.5 mA
          Demagnetization when switching off inductive   By internal varistors
          loads
          Analog Inputs AI                  Max. number per module and with regard to the configuration: AIs / Measuring points
          Signal configuration per AI       4                                 –
          0…10 V / -10…+10 V                4 / 4                             –
          0…20 mA / 4…20 mA                 4 / 4                             –
          RTD using 2/3 wire needs 1/2 channel(s)  4 / 2                      –
          0…10 V using differential inputs,    4 / 2                          –
          needs 2 channels
          -10…+10 V using differential inputs,    4 / 2                       –
          needs 2 channels
          Digital signals (digital input)   4 / 4                             –
          Data when using the AI as digital input
          Input    time delay               8 ms typically, configurable from 0.1 up to 32 ms –
                   signal voltage           24 V DC                           –