Page 514 - Motor_protection_and_control_Manual_motor_starters_ contactors
P. 514

Lighting circuit switching

       Contactor selection AF09 ... AF146  3-pole contactors





       Selection table
       3-pole AC / DC operated contactors  AF09  AF12  AF16  AF26  AF30  AF38  AF40  AF52  AF65  AF80  AF96  AF116 AF140 AF146
       Lamp characteristics    Maximum permissible number of lamps per phase
       W       A       μF

       Metal halide vapour lamps without compensation
       Voltage: 220/240 V AC
       250     3       -       4     5     5     7     7    7     11    14    16    18   20    27    33    38
       400     4       -       3     3     4     5     5    5     8     11    12    13   15    20    25    28
       1000    9.5     -       1     1     1     2     2    2     3     4     5     5    6     8     11    12
       2000    16.5    -       0     0     1     1     1    1     2     2     3     3    3     5     6     7
       Voltage: 380/415 V AC
       2000    10.5    -       1     1     1     2     2    2     3     4     4     5    5     8     10    11
    5  Metal halide vapour lamps with compensation
       Voltage: 220/240 V AC
       250     1.32    33      7     7     7     15    16   17    25    33    37    41   45    69    86    97
       400     2.22    45      5     5     5     9     9    10    14    19    22    24   27    41    51    58
       1000    5.14    85      2     2     3     4     4    4     6     8     9     10   11    18    22    25
       2000    11.5    148     1     1     1     1     1    2     2     3     4     4    5     8     10    11
       Voltage: 380/415 V AC
       2000    6.10    60      2     2     2     3     3    3     5     7     8     9    9     15    19    21











































                                                                                                                  1SBC101961S0201 - Rev. B








       5/314  |  ABB
   509   510   511   512   513   514   515   516   517   518   519