Page 292 - EPR Catalog 2015
P. 292
Analog signal converters - CC-E range
Technical data
Type CC-E/I CC-E IAC/ILPO
C-D
Input circuits - Analog inputs J-G-H
Rated input range 2 meas. ranges selectable
Measuring frequency AC current DC current 0-1 A / 0-5 A / sinusoidal
Overload capacity of inputs 50/60 Hz
0-5 A / 0-20 A 0-5 A / 0-20 A
Gain adjustment range 10 x INom (50 A) for max. 2 s
Offset adjustment range input range 1 10 x INom (50 A) for max. 1 s
Input impedance / resistance 10 x INom (200 A) for max. 2 s
Output circuits - Analog outputs input range 2 10 x INom (200 A) for max. 1 s -
-
±5 % (universal devices) 5 m⏲
F-E passive current output in pro-
±5 % (universal devices)
5A : 65 m⏲ 20 A : 2.5 m⏲
D-F Current A-C Voltage
portion to input current
Output signal 0-20 mA / 0-10 V 4-20 mA
4-20 mA
4 12 V DC: 150 ⏲,
Output burden / load ͨ 500 ⏲ ͧ 1.0 ⏲ 24 V DC: 750 ⏲
30 V DC: 1050 ⏲
Accuracy 1) ± 2 % of full-scale
Offset adjustment range ±5 % (universal device) ±5%
Gain adjustment range ±5 % (universal device) ± 20 %
Residual ripple < 0.5 %
Response time 0.5 s 0.6 s
Transmission frequency DC or 50/60 Hz AC: 50/60 Hz
Reaction to input circuit interruption
Low fail safe: output voltage -
< 200 mV, output current < 400 μA
Supply circuits K-M DC versions AC versions 12-30 V DC
Supply voltage 24 V DC 110-240 V AC -
-15...+15 % 50/60 Hz
Supply voltage tolerance
-15...+10 %
Power consumption typ 1.5 W typ 1.5 VA -
Indication of operational states U: green LED -
Supply voltage
General data 0...+60 °C / -20...+80 °C -20...+60 °C / -40...+80 °C
Ambient temperature rangeoperation / storage ± 500 ppm/°C 300 ppm/°C
Temperature coefficient
Degree of protection (DIN 40050) IP20
Mounting position ventilation slots on top and bottom
Mounting DIN rail (IEC/EN 60715), snap-on mounting
Electrical connection
Wire size rigid 0.2-4 mm² (24-12 AWG)
fine-strand with(out) wire end ferrule 0.2-2.5 mm² (24-14 AWG)
Stripping length 7 mm (0.28 inch)
Tightening torque 0.5 Nm (4.4 lb.in)
Electromagnetic compatibility
Interference immunity EN 61000-6-2
electrostatic discharge (ESD) IEC/EN 61000-4-2 Level 3 (±6 kV / ±8 kV)
electromagnetic field (HF radiation resistance) IEC/EN 61000-4-3 10 V/m
fast transients (Burst) IEC/EN 61000-4-4 Level 3 (±2 kV / 5 kH)
powerful impulses (Surge) IEC/EN 61000-4-5 ±2 kV / ±1 kV
HF line emission IEC/EN 61000-4-6 10 V
Interference emission EN 61000-6-4 Class B
Isolation data
Test voltage (between all isolated circuits) 2.5 kV AC 250 V AC
Rated insulation voltage -
1) Includes non-linearity and factory setting, influenced by supply voltage and output load.
Approvals see „Overview“ on page 4/3
4/13 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210