Current and voltage monitoring relays, single-phase
   Function diagrams

   Function diagrams - CM-ESS.M

   Overvoltage monitoring d without latching e                                                      2CDC 252 228 F0205                      Undervoltage monitoring c without latching e                         2CDC 252 229 F0205

                                A1-A2                                                                                                                                    A1-A2

   Threshold                                                                                                                                Measured value
                                                                                                                                                   Hysteresis
   Hysteresis                                                                                                                                      Threshold

                 Measured value                    < TV              TV         < TV                                                        Open-circuit principle open

2  Open-circuit principle open                                                                                                                               11-14 (15-18)            < TV      TV         < TV
                    11-14 (15-18)                                                                                                                            11-12 (15-16)
                    11-12 (15-16)
                    21-24 (25-28)                                                                                                                            21-24 (25-28)
                    21-22 (25-26)                                                                                                                            21-22 (25-26)

   green LED                                                                                                                                green LED

   red LED                                                                                                                                  red LED

   yellow LED                                                                                                                                                     yellow LED

   Closed-circuit principle closed                                                                                                          Closed-circuit principle closed
                                                                                                                                                               11-14 (15-18)
                      11-14 (15-18)                                                                                                                            11-12 (15-16)
                      11-12 (15-16)                                                                                                                            21-24 (25-28)
                                                                                                                                                               21-22 (25-26)
                      21-24 (25-28)
                      21-22 (25-26)

   green LED                                                                                                                                green LED

   red LED                                                                                                                                  red LED

   yellow LED                                                                                                                               yellow LED

   Overvoltage monitoring d with latching f                                                                                                 Undervoltage monitoring c without latching f

                                A1-A2                                    Reset                                          2CDC 252 230 F0205              A1-A2                                       Reset                            2CDC 252 231 F0205
                                                                                                                                            Measured value
                           Threshold
                          Hysteresis                                                                                                        Hysteresis
                   Measured value
                                                                                                                                            Threshold
     Open-circuit principle open
                      11-14 (15-18)          < TV                TV                   < TV                                                    Open-circuit principle open       < TV        TV             < TV
                      11-12 (15-16)                                                                                                                            11-14 (15-18)
                      21-24 (25-28)                                                                                                                            11-12 (15-16)
                      21-22 (25-26)                                                                                                                            21-24 (25-28)
                          green LED                                                                                                                            21-22 (25-26)
                              red LED
                         yellow LED                                                                                                                                green LED

   Closed-circuit principle closed                                                                                                                                     red LED
                      11-14 (15-18)
                      11-12 (15-16)                                                                                                                               yellow LED
                      21-24 (25-28)
                      21-22 (25-26)                                                                                                         Closed-circuit principle closed
                          green LED                                                                                                                            11-14 (15-18)
                              red LED                                                                                                                          11-12 (15-16)
                         yellow LED                                                                                                                            21-24 (25-28)
                                                                                                                                                               21-22 (25-26)

                                                                                                                                                                   green LED

                                                                                                                                                                       red LED

                                                                                                                                                                  yellow LED

   If the measured value exceeds resp. drops below the adjusted threshold value, the tripping delay TV starts. If TV is complete
   and the measured value is still exceeding resp. below the threshold value plus resp. minus the set hysteresis, the output relays

   energize h / de-energize g.

   If the measured value exceeds resp. drops below the threshold value plus resp. minus the set hysteresis and the latching func-

   tion is not activated e, the output relays de-energize h / energize g. With activated latching function f the output relays

   remain energized h and de-energize only, when the supply voltage is interrupted / the output relays remain de-energized g

   and energize only, when the supply voltage is switched off and then again switched on = Reset. The hysteresis is adjustable

   within a range of 3-30 % of the threshold value.                                                                                                                                                 Further function diagrams see data sheet.

   Voltage window monitoring 1x2 c/o contact j
   ON-delayed A without latching e

                                A1-A2  < TV              TV                              ON-delayed A voltage window monitoring with parallel switching c/o contacts j:2CDC 252 232 F0205

                       Thresholdmax                                                      If the measured value exceeds resp. drops below the adjusted threshold value, the tripping de-
                           Hysteresis
                                                                                < TV
                   Measured value
                                                                                         lay TV starts, when A is configured. If TV is complete and the measured value is still exceeding
                           Hysteresis                                                    resp. below the threshold value minus resp. plus the fixed hysteresis (5%), the output relays
                        Thresholdmin
                                                                                         energize h /de-energize g.
     Open-circuit principle open
                      11-14 (15-18)                                                      If the measured value exceeds resp. drops below the threshold value plus resp. minus the
                      11-12 (15-16)
                      21-24 (25-28)                                                      hysteresis and the latching function is not activated e, the output relays de-energize h /
                      21-22 (25-26)
                          green LED                                                      energize g. With activated latching function e the output relays remain energized h and
                              red LED
                          yellow LED                                                     de-energize only, when the supply voltage is interrupted / the output relays remain de-ener-

   Closed-circuit principle closed                                                       gized g and energize only, when the supply voltage is switched off and then again switched
                      11-14 (15-18)
                      11-12 (15-16)                                                      on = Reset.
                      21-24 (25-28)
                      21-22 (25-26)
                          green LED
                              red LED
                          yellow LED

   Voltage window monitoring 1x2 c/o contact j
   OFF-delayed B without latching e

                                A1-A2                        TV                 2CDC 252 233 F0205OFF-delayed B voltage window monitoring with parallel switching c/o contacts j:

                       Thresholdmax                                                   If the measured value exceeds resp. drops below the adjusted threshold value, the output
                          Hysteresis                                            TV relays energize h / de-energize g, when B is configured, and remain in this position during

                   Measured value                                                     the set tripping delay TV.
                                                                                      If the measured value exceeds resp. drops below the threshold value plus resp. minus the
                          Hysteresis
                        Thresholdmin                                                  fixed hysteresis (5%) and the latching function is not activated e, the tripping delay TV starts.
                                                                                      After completion of TV, the output relays de-energize h / energize g, provided that the latch-
     Open-circuit principle open                                                      ing function is not activated e. With activated latching function e the output relays remain
                      11-14 (15-18)
                      11-12 (15-16)                                                   energized h and de-energize only, when the supply voltage is interrupted / the output relays
                      21-24 (25-28)
                      21-22 (25-26)                                                   remain de-energized g and energize only, when the supply voltage is switched off and then
                          green LED
                              red LED                                                 again switched on = Reset.
                         yellow LED
                                                                                      When i is adjusted on the device, the functionality is equivalent to the one described above.
   Closed-circuit principle closed
                      11-14 (15-18)                                                   There is only to consider that in this case, instead of both output relays, only one output relay
                      11-12 (15-16)
                      21-24 (25-28)                                                   each will be switched.
                      21-22 (25-26)
                          green LED                                                   ā€œ>Uā€œ = 1115-1216/1418 ; ā€œ<Uā€œ = 2125-2226/2428
                              red LED
                         yellow LED