Page 145 - PLC Automation
P. 145

AC500 – HIGH PERFORMANCE MODUL AR PLC                                             143




          —
          AC500
          Technical data




          EtherCAT modules
          Type                              CI511-ETHCAT                      CI512-ETHCAT
          Communication interface
          Protocol                          EtherCAT slave with CAM-Switch configurable function on the digital outputs
          ID Device configuration           Address is defined by position on Ethernet bus
          Field bus connection on TUs       2 x RJ45 with switch functionality for simple daisy chain on TU507-ETH or TU508-ETH
          Number of channels per module
          Digital             inputs        8                                 8
                              outputs       8                                 8
          Analog              inputs        4                                 –
                              outputs       2                                 –
          Digital configurable channels DC (configurable    –                 8
          as inputs or outputs)
          Additional configuration of channels as                                                                     04
          Fast counter (onboard I/O)        –
          Occupies max. 1 DO or DC when used as counter  –
          Connection
          Local I/O extension               
          Max. number of extension modules  max. 10 x S500 extension modules (standard or eCo modules allowed). Fast counter from digital
                                            I/O modules can be also used.
          Via terminal unit TU5xx           
          Digital inputs
          Input signal voltage              24 V DC
          Input characteristic acc. to EN 61 132-2  Type 1
          0 signal                          -3...+5 V DC
          Undefined signal state            5...15 V DC
          1 signal                          15...30 V DC
          Residual ripple, range for  0 signal  -3...+5 V DC
                              1 signal      15...30 V DC
          Input time delay (0 -> 1 or 1 -> 0)   8 ms typically, configurable from 0.1 up to 32 ms
          Digital outputs
          Transistor outputs 24 V DC, 0.5 A  
          Readback of output                –                                  (on DC outputs)
          Outputs, supplied via process voltage UP  
          Switching of 24 V load            
          Output voltage at signal state 1   Process voltage UP - 0.8 V
          Output current
          Nominal current per channel       500 mA at UP = 24 V DC
          Maximum (total current of all channels)   8 A
          Residual current at signal state 0   < 0.5 mA
          Demagnetization when switching off inductive   By internal varistors
          loads
          Analog inputs AI                  Max. number per module and with regard to the configuration: AIs / Measuring points
          Signal configuration per AI       4                                 –
          0…10 V / -10 V… +10 V             4 / 4                             –
          0…20 mA / 4…20 mA                 4 / 4                             –
          RTD using 2/3 wire needs 1/2 channel(s)  4 / 2                      –
          0…10 V using differential inputs,    4 / 2                          –
          needs 2 channels
          -10…+10 V using differential inputs,    4 / 2                       –
          needs 2 channels
          Digital signals (digital input)   4 / 4                             –
          Data when using the AI as digital input
          Input               time delay    8 ms typically, configurable from 0.1 up to 32 ms –
                              signal voltage  24 V DC                         –
   140   141   142   143   144   145   146   147   148   149   150