Page 212 - EPR Catalog 2015
P. 212

CP-D range
Technical data

Data at Ta = 25 °C, Uin = 230 V AC and rated values, unless otherwise indicated

        Type                                                        CP-D 24/0.42             CP-D 24/1.3        CP-D 24/2.5          CP-D 24/4.2
        Input circuit - supply circuit
        Rated input voltage Uin                                                                           L, N
        Input voltage range
        Frequency range AC                                      100-240 V AC

3 Typical input current /                                       90-264 V AC /120-375 V DC
        typical power consumption
                                                                47-63 Hz
        Inrush current limiting
        Power failure buffering time                            at 110 V AC 184 mA / 11.62 W 600 mA / 37.92 W 1120 mA / 69.3 W 1800 mA / 117.3 W
        Internal input fuse
                                                 at 230 V AC 120.6 mA / 12 W 344 mA / 38.16 W 660 mA / 70.1 W 900 mA / 114.4 W
        Power factor correction (PFC)
                                                 at 230 V AC 30 A (max. 3 ms) 50 A (max. 3 ms) 60 A (max. 3 ms)

                                                                min. 30 ms                                  min. 60 ms

                                                                1 A slow-acting 2 A slow-acting /                                3.15 A slow-acting
                                                                                                                                 / 250 V AC
                                                                / 250 V AC             250 V AC

                                                                no

Indication of operational states                 DC ON: green LED V: output voltage applied
Output voltage                                    DC LOW: red LED V: output voltage too low

Output circuit                                                                         +, -                                  ++, --
Rated output voltage
                                                                24 V DC

Tolerance of the output voltage                                 ±1 %

Adjustment range of the output voltage                          - 24-28 V DC

Rated output power                                              10 W                   30 W                 60 W                 100 W

Rated output current Ir                                         Ta ͨ 60 °C: 0.42 A     Ta ͨ 60 °C: 1.3 A    Ta ͨ 55 °C: 2.5 A    Ta ͨ 60 °C: 4.2 A
                                                                                       60 °C < Ta ͨ 70 °C:  55 °C < Ta ͨ 70 °C:  60 °C < Ta ͨ 70 °C:
Derating of the output current                                  60 °C < Ta ͨ 70 °C:    2.5 %/°C             2.5 %/°C             2.5 %/°C
                                                                2.5 %/°C

Maximum                                          load change statical max. 1 %

deviation            change of output voltage within the input voltage range max. 1 %
with

Control time                                                    < 1 ms

Starting time after applying the supply voltage              at Ir 1000 ms
Rise time                                        at rated load typ. 1 ms

Residual ripple and switching peaks              BW = 20 MHz 50 mV

Parallel connection                                             yes, using CP-D RU

Series connection                                               yes, to increase voltage

Resistance to reverse feed                                      35 V / 1 s

Output circuit - No-load, overload and short-circuit behaviour  U/I characteristic curve
Characteristic curve of output
Short-circuit protection                                        continuous short-circuit stability
Short-circuit behaviour
Current limiting at short circuit                               continuation with output power limiting
Overload protection
Overvoltage protection                                          typ. 0.78 A            typ. 4.2 A           typ. 6.05 A          typ. 11.5 A
No-load protection
Starting of capacitive loads                                    output power limiting

                                                                30-33 V DC

                                                                continuous no-load stability

                                                                unlimited

General data                                                    typ. 80 %              typ. 83 %            typ. 86 %            typ. 89 %
Efficiency
Duty time                                                       100 %
Dimensions (W x H x D)
                                                                18 x 91 x 57.5 mm      53 x 91 x 57.5 mm    71 x 91 x 57.5 mm    89.9 x 91 x 57,5 mm
Weight                                                          (0.71 x 3.58 x         (2.09 x 3.58 x       (2.80 x 3.58 x       (3.54 x 3.58 x
Material of housing                                             2.26 in)               2.26 in)             2.26 in)             2.26 in)
Mounting                                                        0.066 kg (0.13 lb)     0.196 kg (0.41 lb)   0.252 kg (0.55 lb)   0.386 kg / (0.72 lb)
Mounting position
Minimum distance to other units                                 plastic
Degree of protection
Protection class                                                DIN rail (IEC/EN 60715), snap-on mounting without any tool

                                                                horizontal

                                                 horizontal / vertical 25 mm / 25 mm (0.98 in / 0.98 in)

                                                 housing / terminals IP20 / IP20

                                                                II

3/13 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210
   207   208   209   210   211   212   213   214   215   216   217