Page 213 - EPR Catalog 2015
P. 213
CP-D range
Technical data
Data at Ta = 25 °C, Uin = 230 V AC and rated values, unless otherwise indicated
Type CP-D 24/0.42 CP-D 24/1.3 CP-D 24/2.5 CP-D 24/4.2
Electrical connection - Input circuit / Output circuit -40…+60 °C
3 kV AC
Wire size fine-strand with wire end ferrule 0.2-1.5 mm2 0.2-2.5 mm2 (24-14 AWG)
Stripping length Level 4
(24-16 AWG) (4 kV / 8 kV)
rigid 0.2-2.5 mm2 0.2-2.5 mm2 (24-12 AWG)
(26-12 AWG)
4-5 mm (0.16-0.2 in) 7 mm (0.28 in)
Tightening torque 0.6 Nm (5 lb.in) 0.7 Nm (6 lb.in) 3
Environmental data
Ambient temperature range operation -40…+70 °C
rated load -40…+60 °C -40…+55 °C
storage -40…+85 °C
Damp heat (cyclic) (IEC/EN 60068-2-30) 4 x 24 cycles, 40 °C, 95 % RH
Vibration (sinusoidal) (IEC/EN 60068-2-6) 50 m/s2, 10 Hz - 2 kHz
Shock (half-sine) (IEC/EN 60068-2-27) 40 m/s2, 22 ms
Isolation data
Rated insulation voltage Ui input circuit / output circuit 3 kV AC 4 kV AC
Pollution degree 2
Overvoltage category (UL/IEC/EN 60950-1) ll
Standards
Product standard EN 61204
Low Voltage Directive 2006/95/EC
EMC Direcitve 2004/108/EC
Electrical safety UL 508, UL 60950-1, EN 60950-1
Protective low voltage SELV (EN 60950-1)
Electromagnetic compatibility
Interference immunity to EN 61000-6-2
electrostatic discharge IEC/EN 61000-4-2 Level 4 Level 4
radiated, radio-frequency, electromagnetic field
(4 kV / 8 kV) (4 kV / 15 kV)
IEC/EN 61000-4-3 Level 3 (10 V/m)
electrical fast transient/burst IEC/EN 61000-4-4 Level 4 (4 kV)
surge IEC/EN 61000-4-5 Level 3 (2 kV L-L)
conducted disturbances, induced by radio- IEC/EN 61000-4-6 Level 3 (10 V)
frequency fields EN 61000-6-3
Interference emission
high-frequency radiated IEC/CISPR 22, EN 55022 Class B
high-frequency conducted IEC/CISPR 22, EN 55022 Class B
„Approvals and marks“ on page 3/4.
2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 3/14