Page 213 - EPR Catalog 2015
P. 213

CP-D range
Technical data

Data at Ta = 25 °C, Uin = 230 V AC and rated values, unless otherwise indicated

Type                                                        CP-D 24/0.42                          CP-D 24/1.3     CP-D 24/2.5          CP-D 24/4.2

Electrical connection - Input circuit / Output circuit                                                                              -40…+60 °C
                                                                                                                                    3 kV AC
Wire size                                  fine-strand with wire end ferrule 0.2-1.5 mm2          0.2-2.5 mm2 (24-14 AWG)
Stripping length                                                                                                                    Level 4
                                                        (24-16 AWG)                                                                 (4 kV / 8 kV)

                                                        rigid 0.2-2.5 mm2                         0.2-2.5 mm2 (24-12 AWG)

                                                        (26-12 AWG)

                                                        4-5 mm (0.16-0.2 in)                                      7 mm (0.28 in)

Tightening torque                                       0.6 Nm (5 lb.in)                                          0.7 Nm (6 lb.in)                  3

Environmental data

Ambient temperature range                               operation -40…+70 °C

                                                        rated load -40…+60 °C                                     -40…+55 °C

                                                        storage -40…+85 °C

Damp heat (cyclic) (IEC/EN 60068-2-30)                  4 x 24 cycles, 40 °C, 95 % RH

Vibration (sinusoidal) (IEC/EN 60068-2-6)               50 m/s2, 10 Hz - 2 kHz

Shock (half-sine) (IEC/EN 60068-2-27)                   40 m/s2, 22 ms

Isolation data

Rated insulation voltage Ui                input circuit / output circuit 3 kV AC                                 4 kV AC
Pollution degree                                                                   2

Overvoltage category (UL/IEC/EN 60950-1)                ll

Standards

Product standard                                        EN 61204

Low Voltage Directive                                   2006/95/EC

EMC Direcitve                                           2004/108/EC

Electrical safety                                       UL 508, UL 60950-1, EN 60950-1

Protective low voltage                                  SELV (EN 60950-1)

Electromagnetic compatibility

Interference immunity to                                EN 61000-6-2

electrostatic discharge                                 IEC/EN 61000-4-2 Level 4                  Level 4
radiated, radio-frequency, electromagnetic field
                                                        (4 kV / 8 kV)                             (4 kV / 15 kV)

                                                        IEC/EN 61000-4-3 Level 3 (10 V/m)

electrical fast transient/burst                         IEC/EN 61000-4-4 Level 4 (4 kV)

surge                                                   IEC/EN 61000-4-5 Level 3 (2 kV L-L)

conducted disturbances, induced by radio-               IEC/EN 61000-4-6 Level 3 (10 V)
frequency fields                                                                    EN 61000-6-3
Interference emission

high-frequency radiated                                 IEC/CISPR 22, EN 55022 Class B

high-frequency conducted                                IEC/CISPR 22, EN 55022 Class B

„Approvals and marks“ on page 3/4.

                                                        2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 3/14
   208   209   210   211   212   213   214   215   216   217   218