Page 226 - EPR Catalog 2015
P. 226
CP-E range
Technical data
Data at Ta = 25 °C, Uin = 230 V AC and rated values, unless otherwise indicated
Type CP-E 48/0.62 CP-E 48/1.25 CP-E 48/5.0 CP-E 48/10.0
Input circuit L, N
Rated input voltage Uin 100-240 V AC 115 / 230 V AC 115-230 V AC
Input voltage range auto select
85-264 V AC / 90-132 V AC, 90-264 V AC,
Frequency range AC 90-375 V DC 180-264 V AC / 120-375 V DC
Typical input current 210-375 V DC
47-63 Hz
at 115 V AC 560 mA 1060 mA 4.0 A 4.9 A
3 at 230 V AC 330 mA 590 mA 1.55 A 2.5 A
Typical power consumption 35.7 W 69.0 W 267 W 528 W
Inrush current limiting at 115 V AC 20 A (max. 3 ms) 20 A (max. 3 ms) 30 A (max. 5 ms) 25 A (max. 5 ms)
at 230 V AC 40 A (max. 3 ms) 40 A (max. 3 ms) 60 A (max. 5 ms) 50 A (max. 5 ms)
Discharge current input / output 0.25 mA
input / PE 3.5 mA
Power failure buffering time at 115 V AC min. 20 ms min. 25 ms min. 25 ms
at 230 V AC min. 30 ms
Internal input fuse 2 A slow-acting / 6.3 A slow- 10 A slow-
Power factor correction (PFC) 250 V AC acting / acting /
250 V AC 250 V AC
no yes, active
yes, passive, 0.7 115 V AC: 0.99
230 V AC: 0.97
Indication of operational states
Output voltage green LED OUTPUT OK: V: output voltage OK
red LED - - OUTPUT LOW: V:
output voltage too low
Output circuit L+, L+, L-, L-
Rated output voltage 48 V DC
Tolerance of the output voltage 0...+1 %
Adjustment range of the output voltage 48-55 V DC 47-56 V DC
Rated output power 30 W 60 W 240 W 480 W
Rated output current Ir Ta ͨ 60 °C 0.625 A 1.25 A 5A -
Derating of the output current Ta ͨ 55 °C - - - 10 A
Signalling output for output voltage OK 60 °C < Ta ͨ 70 °C 2.5 %/°C -
55 °C < Ta ͨ 70 °C - - - 2.5 %/°C
- - -
DC OK -
Maximum deviation with load change statical ±0.5 % ±1 % (single mode)
Control time ±5 % (parallel mode)
change of output voltage within ±0.5 %
the input voltage range ±0.5 %
< 2 ms
Starting time after applying the supply voltage at Ir max. 1 s
with 3500 μF max. 2 s - - -
with 7000 μF - max. 1.5 s max. 1.5 s
Rise time at rated load max. 150 ms
with 3500 μF max. 500 ms - - -
with 7000 μF - max. 500 ms max. 500 ms
Fall time max. 150 ms
Residual ripple and switching peaks BW = 20 MHz 50 mV 100 mV
Parallel connection yes, to enable redundancy configurable, to increase power,
up to 3 devices,
Series connection yes, to increase voltage min. 0.1 Ir - max. 0.9 Ir
Resistance to reverse feed 1 s - max. 63 V DC
yes, to increase voltage,
max. 2 devices
Output circuit - No-load, overload and short-circuit behaviour U/I characteristic curve
Characteristic curve of output
Short-circuit protection continuous short-circuit proof
Short-circuit behaviour
Overload protection continuation with output power limiting
No-load protection
Starting of capacitive loads output power limiting
continuous no-load stability
3500 μF 7000 μF unlimited 7000 μF
3/27 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C0210