Technical data

Data at Ta = 25 °C, Uin = 230 V AC and rated values, unless otherwise indicated

Type                                                                         CP-E 48/0.62 CP-E 48/1.25                CP-E 48/5.0     CP-E 48/10.0

Input circuit                                                                                                L, N

Rated input voltage Uin                                                           100-240 V AC               115 / 230 V AC        115-230 V AC
Input voltage range                                                                                          auto select
                                                                                  85-264 V AC /              90-132 V AC,          90-264 V AC,
Frequency range AC                                                                90-375 V DC                180-264 V AC /        120-375 V DC
Typical input current                                                                                        210-375 V DC
                                                                                  47-63 Hz
                                                                at 115 V AC 560 mA               1060 mA     4.0 A                 4.9 A

3 at 230 V AC 330 mA                                                                             590 mA      1.55 A                2.5 A

Typical power consumption                                                    35.7 W              69.0 W      267 W                 528 W

Inrush current limiting                                         at 115 V AC 20 A (max. 3 ms) 20 A (max. 3 ms) 30 A (max. 5 ms) 25 A (max. 5 ms)

                                                 at 230 V AC 40 A (max. 3 ms) 40 A (max. 3 ms) 60 A (max. 5 ms) 50 A (max. 5 ms)

Discharge current                                input / output 0.25 mA

                                                                input / PE 3.5 mA

Power failure buffering time                                    at 115 V AC min. 20 ms                       min. 25 ms            min. 25 ms

                                                 at 230 V AC min. 30 ms

Internal input fuse                                                          2 A slow-acting /               6.3 A slow-           10 A slow-
Power factor correction (PFC)                                                250 V AC                        acting /              acting /
                                                                                                             250 V AC              250 V AC
                                                                             no                                                    yes, active
                                                                                                             yes, passive, 0.7     115 V AC: 0.99
                                                                                                                                   230 V AC: 0.97

Indication of operational states

Output voltage                                                  green LED OUTPUT OK: V: output voltage OK

                                                                red LED -                        -           OUTPUT LOW: V:
                                                                                                             output voltage too low

Output circuit                                                                                               L+, L+, L-, L-

Rated output voltage                                                         48 V DC

Tolerance of the output voltage                                              0...+1 %

Adjustment range of the output voltage                                       48-55 V DC                      47-56 V DC

Rated output power                                                           30 W                60 W        240 W                 480 W

Rated output current Ir                                     Ta ͨ 60 °C 0.625 A                   1.25 A      5A                    -
Derating of the output current                              Ta ͨ 55 °C -                         -           -                     10 A
Signalling output for output voltage OK          60 °C < Ta ͨ 70 °C 2.5 %/°C                                                       -
                                                 55 °C < Ta ͨ 70 °C -                            -           -                     2.5 %/°C
                                                                                                 -           -                     -
                                                                 DC OK -

Maximum deviation with                           load change statical ±0.5 %                                 ±1 % (single mode)
Control time                                                                                                 ±5 % (parallel mode)
                                         change of output voltage within     ±0.5 %
                                                    the input voltage range                                  ±0.5 %

                                                                             < 2 ms

Starting time after applying the supply voltage                 at Ir max. 1 s

                                                 with 3500 μF max. 2 s                           -           -                     -

                                                 with 7000 μF -                                  max. 1.5 s  max. 1.5 s

Rise time                                        at rated load max. 150 ms

                                                 with 3500 μF max. 500 ms                        -           -                     -

                                                 with 7000 μF -                                  max. 500 ms max. 500 ms

Fall time                                                                    max. 150 ms

Residual ripple and switching peaks              BW = 20 MHz 50 mV                                           100 mV

Parallel connection                                                          yes, to enable redundancy       configurable, to increase power,
                                                                                                             up to 3 devices,
Series connection                                                            yes, to increase voltage        min. 0.1 Ir - max. 0.9 Ir
Resistance to reverse feed                                                   1 s - max. 63 V DC
                                                                                                             yes, to increase voltage,
                                                                                                             max. 2 devices

Output circuit - No-load, overload and short-circuit behaviour               U/I characteristic curve
Characteristic curve of output
Short-circuit protection                                                     continuous short-circuit proof
Short-circuit behaviour
Overload protection                                                          continuation with output power limiting
No-load protection
Starting of capacitive loads                                                 output power limiting

                                                                             continuous no-load stability

                                                                             3500 μF             7000 μF     unlimited             7000 μF